Technical data
Hardware
26 VIPA GmbH CP486 ⋅ 00/14
2.2 Setting of DIP Switches
Setting of DIP Switch S1:
OFF ON
1 PC type selection PLC-115 PLC-135/PLC-155
(NAU/BAU-Signal of X1) (NAU/BAU-Signal of X2)
2 vacant
3 PLC-signal BASP will not be triggers an interrupt
evaluated on the CP486vacant
4 PLC-signal CPKL will not be triggers a RESET
evaluated on the CP486
5 PLC-interrupt IRD off on
6 PLC-interrupt IRC off on
7 PLC-interrupt IRB off on
8 PLC-interrupt IRA off on
Delivery status: 1-2:ON, 3:ON, 8:OFF, 5-8:OFF
Remarks:
The DIP-switch S1/4 must be set to ON, if the module is used in the ZG188.
The DIP-switch S1/3 is not used on the boards (PCB-No.) 5012V14, 5012V15, 5012V16, 5012V17.
The described functions of this switch are available on the boards (PCB-No.) 5012V13, 5012V31....