Technical data
Table Of Contents
- Front Cover
- Table of Contents
- Reference Materials
- Product Overview
- Key Features/Benefits
- Easy to Use Communication and Human Interface Options
- Catalog Number Explanation
- Standard Drive Product Selection
- Factory Installed Options
- User Installed Options
- Product Dimensions
- Installation Considerations
- Cable Recommendations
- Power Ratings and Branch Circuit Protection
- Maximum Motor Cable Lengths
- PowerFlex 700L with 700VC Control, 400V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700VC Control, 480V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700VC Control, 600V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700VC Control, 690V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700S Control, 400V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700S Control, 480V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700S Control, 600V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700S Control, 690V Shielded/Unshielded Cable - Meters (Feet)
- DPI Connections
- Control Connections
- Control Highlights
- Standard Drive Specifications
- Derating Guidelines
- Watts Loss (@ Rated Load, Speed, and PWM Carrier Frequency)
- Cooling Loop Options
- Back Cover/Pub No./Date

PowerFlex 700L Technical Data
18 Publication 20L-TD001A
Frame 3A/3B Drive
Recommended Mounting Clearances
Be sure there is adequate clearance for air circulation around the drive enclosures. A 15 cm (6-in.) minimum clearance is
required wherever vents are located in the cabinet.
Determining Wire Routing for Control, Ground, Drive Input, and Motor Output
All wiring should be installed in conformance with the applicable local, national, and international codes (e.g., NEC/
CEC). Signal wiring, control wiring, and power wiring must be routed in separate conduits to prevent interference with
drive operation. Use grommets, when hubs are not provided, to guard against wire chafing.
Do not route signal and control wiring with power wiring in the same conduit. This can cause interference with drive
operation. Failure to observe this precaution could result in damage to, or destruction of, the equipment.
Do not route more than three sets of motor leads through a single conduit. This will minimize cross-talk that could reduce
the effectiveness of noise reduction methods. If more than three drive/motor connections per conduit are required,
shielded cable must be used. If possible, each conduit should contain only one set of motor leads.
Frame 3A Power Terminal Locations
Coolant Outlet
Coolant Inlet
➊
➌
➍
➋
24 VDC
TB5
DC POSITIVE
DC NEGATIVE
1 120 VAC
2 PRECHARGE COIL
3 120 VAC NEUTRAL
7 INDUCTOR OVERTEMP
WIRE RANGE:
24-10 AWG
(0.2-4 MM)
5 PR HARGE FEEDBACK
GATE ENABLE
STRIP LENGTH:
0.31 IN (8 MM)
TORQUE:
8 IN-LB
(0.9 N-M)