Technical data
Table Of Contents
- Front Cover
- Table of Contents
- Reference Materials
- Product Overview
- Key Features/Benefits
- Easy to Use Communication and Human Interface Options
- Catalog Number Explanation
- Standard Drive Product Selection
- Factory Installed Options
- User Installed Options
- Product Dimensions
- Installation Considerations
- Cable Recommendations
- Power Ratings and Branch Circuit Protection
- Maximum Motor Cable Lengths
- PowerFlex 700L with 700VC Control, 400V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700VC Control, 480V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700VC Control, 600V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700VC Control, 690V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700S Control, 400V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700S Control, 480V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700S Control, 600V Shielded/Unshielded Cable - Meters (Feet)
- PowerFlex 700L with 700S Control, 690V Shielded/Unshielded Cable - Meters (Feet)
- DPI Connections
- Control Connections
- Control Highlights
- Standard Drive Specifications
- Derating Guidelines
- Watts Loss (@ Rated Load, Speed, and PWM Carrier Frequency)
- Cooling Loop Options
- Back Cover/Pub No./Date

PowerFlex 700L Technical Data
42 Publication 20L-TD001A
Liquid-to-Air Heat Exchanger
The liquid-to-air heat exchanger utilizes radiator technology to transfer heat from a liquid to surrounding air. This is a
simple closed loop system — it does not require a water supply from the user. However, this system requires surrounding
air 5 to 10°C below the maximum operating temperature of the drive.
The drawing below shows a cooling loop diagram for a typical liquid-to-air heat exchanger.
The main components of the liquid-to-air heat exchanger cooling loop include:
Part Description
Fan Blows air across the radiator.
Radiator Transfers heat from liquid to air.
Ambient Sensor Senses the ambient temperature used for the dew point control.
Drive Coolant Temperature Sensor Senses the drive coolant temperature used for the dew point control.
Drive Coolant Flow Switch Measures the drive coolant flow rate.
Level Switch Senses the level of coolant in the reservoir.
Reservoir Allows for expansion of coolant.
Pump and Motor Circulates drive coolant.
PowerFlex 700L
Drive
Inlet
Drive
Outlet
Hose Kit
= hose or pipe connection
To
Drive
Inlet
Radiator
From
Drive
Outlet
Liquid-to-Air
Heat Exchanger
Flow
Indicator
Ambient
Sensor
Fan
On/Off
Control
TE
Drive Coolant Temp.
TE
Flow Switch
FS
IN
OUT
Level Switch
Radiator
LS
Reservoir
Drive
IN
OUT
Pump