INSTRUCTION MANUAL Portable Air Conditioner Model: DCP7W For domestic household use only.
IMPORTANT THESE INSTRUCTIONS SHOULD BE READ CAREFULLY AND RETAINED FOR FUTURE REFERENCE. Note also the information presented on the appliance CAUTION: FAILURE TO FOLLOW THESE INSTRUCTIONS MAY CAUSE INJURY AND/ OR DAMAGE AND MAY INVALIDATE YOUR WARRANTY Please read the operating instructions carefully before using your Portable Air Conditioner for the first time and keep them in a safe place. WARNING – This appliance must not be used in a bathroom.
• • • • • • • • • • • WARNING: To avoid danger of suffocation please remove all packaging materials particularly plastic and EPS and keep these away from vulnerable people, children and babies. NEVER drop or insert any object or fingers into any openings. Do not cover or obstruct the air inlet and outlets. Do not use the appliance in locations where paint, petrol or other flammable liquids are used or stored near appliances with continuously operating open flames.
WARNING: For using R290 refrigerant. ThIs symbol shows that this appliance uses a flammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fire. CAUTION: RISK OF FIRE/FLAMMABLE MATERIALS. THE APPLIANCE MUST BE INSTALLED, USED & STORED IN AN AREA THAT IS GREATER THAN 8m2. NB: These symbols on your device mean: • This appliance is filled with Propane gas R290.
• • • 1. 2. 3. 4. 5. 6. • • • • • • • Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants. Please follow the instruction carefully to handle, install, clear, service the air conditioner to avoid any damage or hazard.
• • • • 6 Checks to the refrigeration equipment Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in doubt consult the manufacturer's technical department for assistance.
• • • • • Cabling Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans. Detection of flammable refrigerants Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks.
• • • 8 Decommissioning Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
Exposed to the weather outdoors Near water If the power cable wires are frayed or cut Where small children may be left unattended If an extension lead may become overloaded Where the power cable may be damaged On a slope or uneven surface Where there is risk of fire or close to a naked flame Where it may be damaged by chemicals Where there is a risk of interference by foreign objects This product is not made for DIY repair If there is a risk of water falling on the unit 9
Specification Model no. DCP7W Colour White Power supply 220-240V~, 50Hz Operating temperature 17-35°C Thermostat range 17-30°C Rated Input Power 0.98kW Cooling Capacity 1.93kW Dehumidification Capacity 1.93L/hour Noise Level Minimum (Lo) 51dB(A) Noise Level Maximum (Hi) 62dB(A) Air Volume (Lo/Hi) 211/272 Refrigerant R290 Fan speeds 2 Modes Cool/Fan/Dry Timer 24 hours Dimensions (w x d x h) 329 x 318 x 634mm Min room size 8m2 Max room size 14m2 Weight net 21.
Parts (1) (2) (3) (7) (8) (4) (9) (10) (11) (5) (12) (6) (13) front (1) (2) (3) (4) (5) (6) Control panel Remote signal receptor Horizontal manual louvre control lever Vertical manual louvre control lever Panel Caster rear (7) (8) (9) (10) (11) (12) (13) Handle (both sides) Air filter Upper air intake Drain outlet Air outlet Lower air intake Bottom tray drain outlet Note: All the illustrations in the manual are for explanation purposes only. Your unit may be slightly different.
Control Panel (2) (1) (3) (4) (5) (6) FRESH(Press 3s) (1) (2) (3) (4) (5) (6) Mode button Temp decrease (-) button Indicator light LED display screen Temp increase (+) button Power button Mode button: Selects the appropriate operating mode. Each time you press the button, a mode is selected in a sequence that goes from Cool, Fan, Dry, Heat (on some models), and Auto (on some models). The mode indicator light illuminates under the different mode setting.
LED Display Shows the set temperature while on Cool, Heat or Auto mode (on some models). While on Dry and Fan modes, it shows the room temperature. Error codes: E0 - EEPROM error. E1 - Room temperature sensor error. E2 - Evaporator temperature sensor error. E3 - Condenser temperature sensor error (on some models). E4 - Display panel communication error. EC - Refrigerant leakage detection malfunction (on some models). Protection code: P1 - Bottom tray is full.
Remote Control Mode display AUTO HEAT DRY COOL AUTO FAN COOL HIGH Displayed when data transmitted. DRY MED Displayed when remote controller is ON.
Installation EXHAUST HOSE INSTALLATION The exhaust hose and adaptor must be installed or removed in accordance with the usage mode. For COOL, HEAT (heat pump type) or AUTO (on some models) mode the exhaust hose must be installed. For FAN, DRY or HEAT (electrical heat type) the exhaust hose should be removed. EXHAUSTING HOT AIR In COOL function the appliance must be placed close to a window or opening so the warm exhaust air can be expelled outside.
Installation WINDOW KIT INSTALLATION The window slider kit has been designed to fit most standard vertical and horizontal window applications, however it may be necessary for you to modify some aspects of the installation procedures for certain types of windows. Step one: Preparing the exhaust hose assembly Press the exhaust hose (or extended exhaust hose) into the window slider adaptor (or wall exhaust adaptor) and unit adaptor, clamp automatically by the elastic buckles of the adaptors.
Installation WINDOW KIT INSTALLATION Step two: Install the exhaust hose assembly to the unit Push the Exhaust hose into the air outlet opening of the unit along the arrow direction. Step three: Preparing the adjustable window slider 1. Choose the window sliders according the size of your window. If the sliders need to be cut to meet the window size, please take extra care to cut it properly. 2. Use bolts to fasten the window sliders once they are adjusted to the correct length.
Installation WINDOW KIT INSTALLATION Before assembl y MODEL B Window Sliders After assembl y Bolt 1+2: Bolt Bolt 1+2+3 : Bolt Bolt 1+2+3+4 : Bolt 1+4: MODEL C Before assembl y Window Sliders After assembl y Bolt 1+2: Bolt 1+2+3 : 18 Bolt Bolt
Installation WINDOW KIT INSTALLATION Note: Once the exhaust hose assembly and adjustable window lider are prepared, choose from one of the following two installation methods. Type 1: Hung Window or Sliding Window Installation (for some models) Foam seal B (Adhesive type-shorter) Foam seal B (Adhesive type-shorter) Or Foam seal A (Adhesive type) Foam seal A (Adhesive type) 1. Cut the adhesive foam seal A and B strips to the proper lengths, and attach them to the window sash and frame as shown.
Installation Or 5. I nsert the window slider adaptor into the hole of the window slider. Type 2: Wall Installation (for some models) 1. Cut a 125mm (4.9inch) hole into the wall for wall exhaust adaptor B. 2. Secure the wall exhaust adaptor B to the wall using the four anchors and screws provided in the kit. 3. Connect the exhaust hose assembly (with wall exhaust adaptor A) to the wall exhaust adaptor B.
Installation TOOLS NEEDED • Medium Philips screwdriver • Tape measure or ruler • Knife or scissors • Saw (optional, to shorten window kit for narrow windows ACCESSORIES (not all accessories supplied with all models) Name of Accessories Qty. Shape Name of Accessories Qty.
Operating Instructions COOL operation · Press the "MODE" button until the "COOL" indicator light comes on. · Press the ADJUST buttons "+" or "-" to select your desired room temperature. The temperature can be set within a range of 17°C~30°C/62°F~88°F(or 86°F). · Press the "FAN SPEED" button to choose the fan speed. DRY operation · Press the "MODE" button until the "DRY" indicator light comes on. · The fan speed or the temperature cannot be adjusted. The fan motor operates at LOW speed.
Operating Instructions Constant Fan button (On some models) In Cooling or Dry mode, press the button for 3 seconds to turn on or off the constant fan function. When the function is turned on, the constant fan light will illuminate, identifying the fan continuous run for cooling. When the function is turned off, the constant fan light will go out, identifying the fan cycle run with compressor stop.
Operating Instructions POWER MANAGEMENT feature (On some models) Under cooling operation, when the ambient temperature is lower than the setting temperature for a period of time, the unit will automatically operate the power management feature. The compressor and fan motor will stop. When the ambient temperature is higher than the setting temperature, the unit will automatically quit the power management feature. The compressor and (or) fan motor will run.
Continuous drain hose Remove thedrainplug When the water level of the bottom tray reaches a predetermined level, the unit beeps 8 times, the digital display area shows "P1" . At this time the air conditioning/ dehumidification process will immediately stop. However, the fan motor will continue to operate (this is normal). Carefully move the unit to a drain location, remove the bottom drain plug and let the water drain away.
Cleaning SAFETY PRECAUTIONS • Always unplug the unit before cleaning or servicing. • DO NOT use flammable liquids or chemicals to clean the unit. • DO NOT wash the unit under running water. Doing so causes electrical danger. • DO NOT operate the machine if the power supply was damaged during cleaning. A damaged power cord must be replaced with a new cord from the manufacturer. AIR FILTERS CAUTION: Never operate the unit without a filter in place.
Maintenance Storage If not using the unit for an extended period of time, after cleaning please: • Turn the unit OFF, unplug and take care of the mains lead & plug. • Drain any water from the unit according to the instructions in the following sections. • Run the appliance on FAN MODE for 12 hours in a warm room to dry out and prevent mould. • Clean the air filter as described on the previous page. • Remove the batteries from the remote control.
Customer Care: 1300 556 816 customer.care@glendimplex.com.au www.dimplex.com.au Supplied by Glen Dimplex Australia 8 Lakeview Drive, Scoresby, Victoria, 3179 © Glen Dimplex Australia. All rights reserved. Material contained in this publication may not be reproduced in whole or in part, without prior permission in writing of Glen Dimplex Australia.