Technical data

www.dimplex.de/en
20
2012
Built-under buffer tank
PSP 140E
Nominal capacity 140 l; in air-to-water heat pump design to enable space-saving installation on top of the built-under buffer;
polyurethane insulation with minimal downtime losses (can be used for heating and cooling), incl. 2½“ sleeves for immersion heaters
(up to CTHK 636); 1“ heating water connections; colour: white; brown red design screen.
Order reference Art.-no. For device type Width x Height x Depth
mm
Weight
kg
PSP 140E 353970
LI 11 - LI 20TE(S) 750 x 600 x 880 72
PSP 140E 353970 4015627353978
Max. flow temperature 58 °C
Casing colour White (similar to RAL 9003)
Low temperature air-to-water heat pump
Universal design with two performance levels
LI 20-28TE
Heat pump for heating purposes for indoor installation with integrated WPM 2007 plus controller. The control panel is integrated into
a brown-red design screen and can also be used as wired remote control using the wall mounting set (special accessories MS PGD). The
integrated air circuit enables corner or wall installation with air ducts at the air intake and the air outlet side. Sound-optimised through
low-noise axial fan and vibration-isolated compressor. High coefficients of performance (COP) using an evaporator optimised for heating
operation and energy-efficient defrosting by reverse circulation. Universal design with two compressors for output reduction when
operating at partial load, optional domestic hot water preparation and flexible expansion options for:
Bivalent or bivalent-renewable operating mode
Distribution systems with unmixed and mixed heating circuits
Soft starter, integrated flow and return sensors; external sensor (standard NTC-2) included in the scope of supply.
Lower operating limit heat source (heating operation) -25 °C ; Upper operating limit heat source (heating operation) 35 °C ; Refrigerant
R404A ; Control voltage ~230 V ; Connection heating 1¼ ˝ ; Connection voltage 3/N/PE ~400 V, 50 Hz
Order reference Art.-no. Heat output
1 compressor /
COP A2/W35
Heat output
2 compressors /
COP A2/W35
Air outlet Width x Height x Depth
mm
Weight
kg
LI 20TE 352670
8.6 / 3.1 14.6 / 3 .0
Right
750 x 1570 x 880 255
LI 24TE 352690
10.5 / 3 .0 18.7 / 3.1
750 x 1710 x 1030
310
LI 28TE 352710
12.4 / 3 .0 20.8 / 3.1 314
Heat output and COP according to EN 14511 at A2/W35.
LI 20TE 352670 4015627352674
LI 24TE 352690 4015627352698
LI 28TE 352710 4015627352711
Max. flow temperature 75 °C
Casing colour White (similar to RAL 9003)
High temperature air-to-water heat pump
Universal design with low temperature and high temperature levels
LIH 26TE
Heat pump for heating purposes for indoor installation with integrated WPM 2007 plus controller. The control panel is integrated into
a brown-red design screen and can also be used as wired remote control using the wall mounting set (special accessories MS PGD). The
integrated air circuit enables corner or wall installation with air ducts at the air intake and the air outlet side. Sound-optimised through
low-noise axial fan and vibration-isolated compressor. High coefficients of performance (COP) using an evaporator optimised for heating
operation and energy-efficient defrosting by reverse circulation. Universal design with low temperature and high temperature levels,
optional domestic hot water preparation and the possibility of flexible expansion for:
Bivalent or bivalent-renewable operating mode
Distribution systems with unmixed and mixed heating circuits
In the summer a maximum flow temperature of 58 °C is available for domestic hot water preparation. Soft starter, integrated flow and
return sensors; external sensor (standard NTC-2) included in the scope of supply.
Lower operating limit heat source (heating operation) -25 °C ; Upper operating limit heat source (heating operation) 35 °C ;
Refrigerant R404A ; Refrigerant R134a ; Control voltage ~230 V ; Connection heating 1¼ ˝ ; Connection voltage 3/N/PE ~400 V, 50 Hz
Order reference Art.-no. Heat output 1 compressor /
COP A2/W35
Heat output with 2 compressor /
COP A-7/W45
Width x Height x Depth
mm
Weight
kg
LIH 26TE 352740
15.7 / 3 .0 15.2 / 2.2 750 x 1710 x 1030 377
Heat output and COP according to EN 14511 at A2/W35.
Heat output with 2 compressors and coefficient of performance (COP) according to EN 14511 at A7/W45 .
The maximum flow temperature of 75 °C is reached at an air intake temperature from -25 °C to +10 °C (high temperature level).
At outdoor temperatures above 10 °C, the maximum flow temperature is +58 °C (low temperature level) .
LIH 26TE 352740 4015627352742
Max. flow temperature 58 °C
Casing colour White
Low temperature air-to-water heat pump
For wall installation with two performance levels
LI 40AS
Heat pump for heating purposes for indoor installation with wall-mounted WPM 2006 Plus heat pump manager and two compressors for
output reduction when operating at partial load. The air is drawn in via the heat pump installed directly in front of the wall. The air circuit
on the air outlet side is established via air ducts. Sound-optimised through low-noise, low-speed axial fan and encapsulated compressor
housing; energy-efficient defrosting by reverse circulation. High coefficients of performance (COP) through high-performance evapora-
tor and compliance with the requirements of EN 14511 for larger volume flows on the heat consumption side. Universal design with two
compressors for modulating operation, optional domestic hot water preparation and flexible expansion options for:
Bivalent or bivalent-renewable operating mode
Distribution systems with unmixed and mixed heating circuits
Integrated soft starter and flow sensors; return and external sensors (standard NTC-2) included in the scope of supply.
Electrical connection line EVL 996-1 (10 m) between heat pump and heat pump manager included in the scope of supply.
Lower operating limit heat source (heating operation) -25 °C ; Upper operating limit heat source (heating operation) 35 °C ;
Refrigerant R404A ; Control voltage ~230 V ; Connection heating 1½ ˝ ; Connection voltage 3/N/PE ~400 V, 50 Hz
Order reference Art.-no. Heat output
1 compressor /
COP A2/W35
Heat output
2 compressors /
COP A2/W35
Air outlet Width x Height x Depth
mm
Weight
kg
LI 40AS 358300
16.8 / 3.9 30.0 / 3.8 Fan side 1735 x 2100 x 890 590
Heat output and COP according to EN 14511 at A2/W35.
LI 40AS 358300 4015627358300
Air-to-water heat pump for indoor installation