Technical data
www.dimplex.de/en
24
2012
Heat pump for heating purposes - ground as heat source
High-efficiency brine-to-water heat pump
Max. flow temperature 62 °C
Casing colour White (similar to RAL 9003)
High-efficiency brine-to-water heat pump
Universal design with solid-borne sound insulation
SI 11TU
Heat pump for heating purposes for indoor installation with integrated WPM EconPlus. Variable connection options for brine and hea-
ting connections on the back board of the casing. Integrated solid-borne sound insulation for direct connection to the heating system.
Sound-optimised through encapsulated compressor housing and free-swinging compressor baseplate. High coefficients of performance
(COPs) thanks to electronic expansion valve, COP booster and compliance with the requirements of EN 14511 for larger volume flows on
the heat consumption side. Sensor monitoring of the refrigeration circuit for a high degree of operational safety and integrated thermal
energy metering (display of the calculated quantity of thermal energy for heating and domestic hot water preparation on the WPM
EconPlus heat pump manager). The control panel is integrated into a brown-red design screen and can also be used as wired remote
control using the wall mounting set (special accessories MS PGD). Universal design with optional domestic hot water preparation and
flexible expansion possibilities for:
• Bivalent or bivalent-renewable operating mode
• Distribution systems with unmixed and mixed heating circuits
Soft starter, integrated flow and return sensors; external sensor (standard NTC-2) included in the scope of supply.
High-efficiency brine package with electronic control of the brine pump and the brine circuit manifold must be ordered separately.
Lower operating limit heat source (heating operation) -5 °C ; Upper operating limit heat source (heating operation) 25 °C ;
Refrigerant R410A
Order reference Art.-no. Heat output 1 compressor /
COP at B0/W35
Connection voltage Width x Height x Depth
mm
Weight
kg
SI 6TU 364080
6.1 / 4.7
3/PE ~400 V, 50 Hz
650 x 845 x 565
119
SI 8TU 364090
8.1 / 4.8 128
SI 11TU 364100
10.9 / 4.9 134
SI 14TU 364110
13.9 / 5 .0 140
SI 18TU 364120
17.5 / 4.7 650 x 845 x 665 163
Heat output and coefficient of performance (COP) according to EN 14511 at B0/W35 .
If commissioning is carried out by the after-sales service and the antifreeze contains 30% monoethylene glycol, the lower operating limit can be
expanded to -10 °C!
SI 6TU 364080 4015627364080
SI 8TU 364090 4015627364097
SI 11TU 364100 4015627364103
SI 14TU 364110 4015627364110
SI 18TU 364120 4015627364127
Supporting feet for high-efficiency brine-to-water heat pump
STF 4
Supporting feet for fitting to the brine-to-water heat pumps and the water-to-water heat pumps in the TU series. The supporting feet are
fitted to the bottom of the heat pump, enabling it to be installed level, even if the floor is uneven. Scope of supply: 4 units.
Order reference Art.-no. For device type Weight
kg
STF 4 364960
WI 10TU - WI 14TU
SI 6TU - SI 18TU
1
Using the supporting feet increases the sound power level of the heating pump by 3 dB(A).
STF 4 364960 4015627364967
Max. flow temperature 58 °C
Casing colour White (similar to RAL 9003)
Low temperature brine-to-water heat pump
Universal design
SI 22TU
Heat pump for heating purposes for indoor installation with integrated WPM EconPlus. Variable connection options for brine and hea-
ting connections on the back board of the casing. Integrated solid-borne sound insulation for direct connection to the heating system.
Sound-optimised through insulated metal casing and double vibration-isolated compressor. High coefficients of performance (COP) with
economiser and compliance with the requirements of EN 14511 for larger volume flows on the heat consumption side. Sensor monito-
ring of the refrigeration circuit for a high degree of operational safety and integrated thermal energy metering (display of the calculated
quantity of thermal energy for heating and domestic hot water preparation on the WPM EconPlus heat pump manager). The control
panel is integrated into a brown-red design screen and can also be used as wired remote control using the wall mounting set (special
accessories MS PGD). Universal design with optional domestic hot water preparation and flexible expansion possibilities for:
• Bivalent or bivalent-renewable operating mode
• Distribution systems with unmixed and mixed heating circuits
Soft starter, load contactor for brine circulating pump, integrated flow and return sensor; external sensor (standard NTC-2) and dirt filter
for brine circuit included in the scope of supply.
Brine package and brine circuit manifold must be ordered separately.
Lower operating limit heat source (heating operation) -5 °C ; Upper operating limit heat source (heating operation) 25 °C ;
Refrigerant R407C
Order reference Art.-no. Heat output 1 compressor /
COP at B0/W35
Connection voltage Width x Height x Depth
mm
Weight
kg
SI 22TU 362340
22.9 / 4.3 3/PE ~400 V, 50 Hz 650 x 845 x 665 184
Heat output and coefficient of performance (COP) according to EN 14511 at B0/W35.
SI 22TU 362340 4015627362345