Technical data
www.dimplex.de/en
41
2012
Max. flow temperature 58 °C
Flow temperature cooling min. 7 °C
Casing colour White (similar to RAL 9003)
Reversible brine-to-water heat pump
Optimised for heating and cooling with waste heat recovery
SI 130TUR+
Heat pump for heating and cooling with integrated regulation installed indoors. Variable connection options for brine and heating
connections on the back board of the casing. Access for service work from the front, no minimum clearance required on the sides, acces-
sible from underneath with a lift truck. A sound-optimised insulated metal casing and the integrated solid-borne sound insulation with
free-swinging compressor base plate make direct connection with the heating system possible. High coefficients of performance (COP)
thanks to compliance with EN 14511 for larger volume flows on the heat consumption side. Optimised heating and cooling operation via
an external four-way reversing valve which is activated by the controller (special accessory). Reversible refrigeration circuit with addi-
tional heat exchanger for higher domestic hot water temperatures in heating operation and waste heat recovery in cooling operation.
Sensor monitoring of the refrigeration circuit for a high degree of operational safety and integrated thermal energy metering (display of
the calculated quantity of thermal energy for heating and domestic hot water preparation on the WPM EconPlus heat pump manager).
The control panel is integrated into a brown-red design screen and can also be used as wired remote control using the wall mounting set
(special accessories MS PGD). Universal design with flexible expansion options for:
• Bivalent or bivalent-renewable operating mode
• Combined distribution systems for heating and cooling
• Unmixed and mixed heating and cooling circuits
• Combination of active and passive cooling (special accessory)
Silent cooling via panel heating/cooling systems requires the use of the room climate station (special accessory) to regulate the flow
temperature on the basis of the air temperature and humidity of a reference room. Soft starter, load contactor for brine circulating pump,
integrated flow and return sensor; external sensor (standard NTC-2) and dirt filter for brine circuit included in the scope of supply.
Lower operating limit heat source (heating operation) -5 °C ; Upper operating limit heat source (heating operation) 25 °C ; Lower opera-
ting limit heat source (cooling operation) 10 °C ; Upper operating limit heat source (cooling operation) 30 °C ; Refrigerant R410A ; Connec-
tion voltage 3/N/PE ~400 V, 50 Hz
Order reference Art.-no. Heat output
1 compressor /
COP B0/W35
Heat output
2 compressors /
COP B0/W35
Cooling capacity
2 compressor /
EER B20/W10
Width x Height x Depth
mm
Weight
kg
SI 130TUR+ 361770
57.6 / 4.4 108.5 / 4.2 129.0 / 5.6 1350 x 1890 x 775 830
Heat output and coefficient of performance (COP) according to EN 14511 at B0/W35.
Cooling capacity and coefficient of performance (COP) according to EN 14511.
A water-to-water heat pump must be used for borehole heat exchangers with water as the heat transfer medium. The SI 130TUR+ is also available
upon request in a WI 140TUR+ version, which works with water as the heat source.
The performance levels stated can only be achieved in combination with the external four-way valve available as a special accessory.
Delivery time on request.
SI 130TUR+ 361770 4015627361775
Four-way reversing valve, rev. brine-to-water heat pump
Special hydraulic accessories for cooling
VWU 65
The four-way reversing valve (DN 65 flange or DN 80 flange) for integration into the flow allows optimised heating and cooling operation
of the SI 130TUR+ reversible brine-to-water heat pump. Switching takes place via a pre-assembled electromotive actuator (1/N/PE ~230
V) which is activated by the WPM EconR heat pump manager.
Order reference Art.-no. For device type Maximum volume flow
m³/h
Features Weight
kg
VWU 65 362760
SI 130TUR+
2 0
Four-way reversing valve for switching from
heating to cooling operation in flow and/or
return. Actuator, 3-point control signal, 1/N/
PE ~230 V, 50 Hz for short switching times.
15
VWU 80 362770
25 23
VWU 65 362760 4015627362765
VWU 80 362770 4015627362772
Flow switch
SI 130TUR+ brine-to-water heat pump
DFS 80
DN 80 external thread/external thread pipe assembly with flow switch (switch point at 6.5 m
3
/h ± 10%) for SI 130TUR+ brine-to-water
heat pumps. Can be used for flow rate monitoring in the heating circuit and in the brine circuit.
Order reference Art.-no. For device type Switch point
m³/h
Connection heating
˝
Weight
kg
DFS 80 361840
SI 130TUR+ 6.5 3 .0 3
DFS 80 361840 4015627361843
Heating and cooling - ground/ground water as heat source