Technical data

www.dimplex.de/en
10
2012
Low temperature air-to-water heat pump
Max. flow temperature 55 °C
Casing colour White aluminium (similar to RAL 9006)
Low temperature air-to-water heat pump
For installation close to walls
LA 11MAS
Air-to-water heat pump for outdoor installation with external temperature controlled WPM 2006 plus heat pump manager.
Sound-optimised through the use of low-noise ‚owl‘s wings‘ ventilator blades. Energy-efficient defrosting by reverse circulation.
High coefficients of performance (COP) thanks to compliance with EN 14511 for larger volume flows on the heat consumption side.
Universal design with optional domestic hot water preparation and flexible expansion possibilities for:
Bivalent or bivalent-renewable operating mode
Distribution systems with unmixed and mixed heating circuits
The minimum clearances must be observed for installation close to walls. Integrated flow sensor and soft starter; return sensor and
external temperature sensor included in the scope of supply.
The EVL . . . electric cable for connecting the heat pump and the heat pump manager, must be ordered separately.
Lower operating limit heat source (heating operation) -25 °C ; Upper operating limit heat source (heating operation) 35 °C ; Refrigerant
R404A ; Control voltage ~230 V ; Connection heating 1 ˝ ; Connection voltage 1/N/PE ~230 V, 50 Hz
Order reference Art.-no. Heat output 1 compressor /
COP A2/W35
Connection voltage Width x Height x Depth
mm
Weight
kg
LA 11MAS 363760
7.9 / 3.4
1/N/PE ~230 V, 50 Hz
1050 x 1340 x 852 189
LA 16MAS 363770
11.9 / 3.1 1074 x 1550 x 852 229
Heat output and COP according to EN 14511 at A2/W35.
The air outlet must be positioned at a right angle to the main wind direction if unsheltered outdoor installation is carried out.
LA 11MAS 363760 4015627363762
LA 16MAS 363770 4015627363779
Max. flow temperature 58 °C
Casing colour White aluminium (similar to RAL 9006)
Low temperature air-to-water heat pump
For installation close to walls
LA ..TAS
Air-to-water heat pump for outdoor installation with external temperature controlled WPM 2006 plus heat pump manager.
Sound-optimised through the use of low-noise ‚owl‘s wings‘ ventilator blades. Energy-efficient defrosting by reverse circulation.
High coefficients of performance (COP) thanks to compliance with EN 14511 for larger volume flows on the heat consumption side.
Universal design with optional domestic hot water preparation and flexible expansion possibilities for:
Bivalent or bivalent-renewable operating mode
Distribution systems with unmixed and mixed heating circuits
The minimum clearances must be observed for installation close to walls. Integrated flow sensor and soft starter; return sensor and
external temperature sensor included in the scope of supply.
The EVL . . . electric cable for connecting the heat pump and the heat pump manager, must be ordered separately.
Lower operating limit heat source (heating operation) -25 °C ; Upper operating limit heat source (heating operation) 35 °C ;
Refrigerant R404A ; Control voltage ~230 V ; Connection heating 1˝ ; Connection voltage 3/N/PE ~400 V, 50 Hz
Order reference Art.-no. Heat output 1 compressor /
COP A2/W35
Connection voltage Width x Height x Depth
mm
Weight
kg
LA 11TAS 362570
8.6 / 3.4
3/N/PE ~400 V, 50 Hz
1050 x 1340 x 852 193
LA 16TAS 362580
11.7 / 3.2 1075 x 1550 x 852 231
Heat output and COP according to EN 14511 at A2/W35.
The air outlet must be positioned at a right angle to the main wind direction if unsheltered outdoor installation is carried out.
LA 11TAS 362570 4015627362574
LA 16TAS 362580 4015627362581
Air-to-water heat pump for outdoor installation
Max. flow temperature 58 °C
Flow temperature cooling min. 7 °C
Casing colour White aluminium (similar to RAL 9006)
Reversible air-to-water heat pump
Optimised for heating operation
LA 11MSR
Air-to-water heat pump for outdoor installation with external temperature controlled WPM 2006 R heat pump manager and reversible
refrigeration circuit for heating and cooling. Sound-optimised through the use of low-noise crescent wing axial fans and deflector hoods.
Energy-efficient defrosting by reverse circulation und diagonally positioned evaporator. Universal design with optional domestic hot
water preparation and flexible expansion possibilities for:
Bivalent operation (bivalent-renewable not possible)
Combined distribution systems for heating and cooling
Unmixed and mixed heating and cooling circuits
Silent cooling via panel heating/cooling systems requires the use of the room climate station (special accessory) to regulate the flow
temperature on the basis of the air temperature and humidity of a reference room.
The EVL . . R electric cable for connecting the heat pump and the heat pump manager must be ordered separately.
Lower operating limit heat source (heating operation) -20 °C ; Upper operating limit heat source (heating operation) 35 °C ;
Lower operating limit heat source (cooling operation) 15 °C ; Upper operating limit heat source (cooling operation) 40 °C ;
Refrigerant R404A ; Control voltage ~230 V ; Connection heating 1˝ ; Connection voltage 1/N/PE ~230 V, 50 Hz
Order reference Art.-no. Heat output
1 compressor /
COP A2/W35
Cooling capacity
1 compressor /
EER A27/W7
Connection
heating
˝
Width x Height x Depth
mm
Weight
kg
LA 11MSR 342690
8.8 / 3.3 8.8 / 2.8 1 1360 x 1360 x 860 224
Heat output and COP according to EN 14511 at A2/W35.
Cooling capacity and coefficient of performance (EER) according to EN 14511.
If sound protection requirements are very high, we recommend installing double-sphere rubber expansion joints between the heat pump and the
heating system in order to optimise solid-borne sound insulation. KOMP expansion joints available as special accessories.
LA 11MSR 342690 4015627342699