Specifications

www.dimplex.co.uk/quantum
Dimplex Quantum
Heater sizing guide
Dimplex provides a number of options,
to meet different property and timescale
requirements. If you need to obtain an
indication of the heating requirements for
estimating or if you need heating for one or
two rooms, please use this Selection Guide.
Alternatively use our online calculator
at www.dimplex.co.uk/heatdesign
For single properties, please complete
the form on our website (also at
www.dimplex.co.uk/heatdesign)
and send it with a sketch plan to
our heating design department.
We aim to provide an accurate
assessment within 7 working days.
For multiple properties, please send us
comprehensive scale drawings (scale
1:50 or 1:100) together with construction
details and any other relevant information.
We offer a 14 working day service for
this type of assessment.
Our contact details are:
email: heat.design@dimplex.co.uk
Heating Design Team, Dimplex,
Millbrook House, Grange Drive,
Hedge End, Southampton SO30 2DF
The tables below provide heater sizing
guidance for Quantum heaters. Knowing
the floor area, the wall construction and
the number of outside walls, the heater
loading in kilowatts is indicated in the
appropriate table. These tables do not
take into account particularly old
properties or those built very recently.
If your property fits into one of these
classifications, please complete the
form on our website so that we can
provide a more accurate assessment.
Living or dining room: Quantum
Heater loading in kW. Temperature 21°C
Floor
area
Solid walls
no. of outside walls
Cavity walls
no. of outside walls
Insulated cavity walls
no. of outside walls
m
2
1 2 3 1 2 3 1 2 3
12 1.84 2.16 2.88 1.60 1.92 2.48 1.12 1.28 1.68
16 2.08 2.48 3.20 1.84 2.32 2.88 1.36 1.60 1.92
20 2.64 3.12 3.92 2.32 2.72 3.44 1.68 1.92 2.32
24 2.96 3.44 4.32 2.64 3.12 3.76 2.08 2.32 2.64
28 3.28 3.92 4.80 2.96 3.44 4.24 2.16 2.48 2.96
32 3.52 4.32 5.28 3.28 3.76 4.72 2.40 2.72 3.20
Commercial heating For greater control and economy of operation Quantum heaters
are recommended. Sizing is based on a single storey with a ceiling height of 3m and
a minimum of 75mm of roof insulation.
Office: Quantum
Heater loading in kW. Temperature 21°C
Floor
area
Solid walls
No. of outside walls
Cavity walls
No. of outside walls
Insulated cavity walls
No. of outside walls
m
2
1 2 3 1 2 3 1 2 3
15 2.16 2.96 4.08 2.00 2.56 3.52 1.68 2.08 2.64
20 2.64 3.52 4.48 2.40 3.12 4.00 2.08 2.56 3.12
25 2.96 4.08 5.20 2.72 3.68 4.56 2.40 3.04 3.60
30 3.52 4.72 5.84 3.36 4.24 5.20 2.88 3.52 4.16
40 4.80 5.92 7.68 4.40 5.36 6.72 3.92 4.48 5.36
50 5.28 6.80 8.40 4.96 6.24 7.44 4.48 5.28 6.08
Kitchen: Quantum
Heater loading in kW. Temperature 18°C
Floor
area
Solid walls
no. of outside walls
Cavity walls
no. of outside walls
Insulated cavity walls
no. of outside walls
m
2
1 2 3 1 2 3 1 2 3
10 1.28 1.68 2.32 1.12 1.60 1.92
For all kitchens with
cavity wall insulation
direct heating is preferred.
12 1.52 2.16 2.64 1.36 1.84 2.32
14 1.68 2.40 2.88 1.60 2.08 2.48
16 1.92 2.64 3.12 1.68 2.32 2.72
Bedrooms: For bedrooms panel heaters are recommended.
Heater loading in kW. Temperature 18°C
Floor
area
Solid walls
no. of outside walls
Cavity walls
no. of outside walls
Insulated cavity walls
no. of outside walls
m
2
1 2 3 1 2 3 1 2 3
8 0.8 1.3 1.7 0.8 1.0 1.4 0.8 0.9 1.4
12 0.9 1.8 2.3 0.9 1.4 2.1 0.8 1.4 1.8
16 1.2 2.1 2.7 1.0 1.7 2.2 0.9 1.6 2.1
20 1.4 2.2 3.1 1.2 2.0 2.6 1.0 1.8 2.4
24 1.5 2.3 3.4 1.2 2.1 2.9 1.0 1.9 2.5
15
Quantum Cylinder. Technical specifications.