Installation manual
www.dimplex.de 131
Water-to-Water Heat Pump 4.6.1
4.6 Device Information for Water-to-Water Heat Pumps (3-Phase, 400 V AC)
4.6.1 Low-temperature heat pumps WI 9TE to WI 27TE
Device information for water-to-water heat pumps (heating only)
1 Type and order code
WI 9TE WI 14TE WI 18TE WI 22TE WI 27TE
2Design
2.1 Degree of protection according to EN 60 529 IP20 IP20 IP20 IP20 IP20
2.2 Installation Location Indoors Indoors Indoors Indoors Indoors
3 Performance data
3.1 Operating temperature limits:
Heating water flow °C Up to 58 Up to 58 Up to 58 Up to 58 Up to 58
Cold water (heat source) ° C +7 to +25 +7 to +25 +7 to +25 +7 to +25 +7 to +25
3.2 Temperature spread of heating water at W10 / W35K 9.5 5.0 8.8 5.0 9.2 5.0 9.6 5.0 9.4 5.0
3.3 Heat output / COP at W7 / W55
1
kW / ---
1. This data indicates the size and capacity of the system according to EN 255 or EN 14511. For an analysis of the economic and energy efficiency of the system, bivalence point
and regulation should also be taken into consideration. The specified values, e.g. W10 / W55, have the following meaning: Heat source temperature 10 °C and heating water flow
temperature 55 °C.
6.9 /
2.5
12.2 /
2.5
14.9 /
3.0
19.0 /
3.2
24.6 /
3.2
at W10 / W50
1
kW / ---
7.7 /
3,2
13.4 /
3.6
16.3 /
3.7
20.8 /
3.8
26.4 /
3.8
at W10 / W45
1
kW / ---
7.6 /
3.5
13.2 /
3.8
16.1 /
4.0
20.5 /
4.0
26.0 /
4.1
at W10 / W35
1
kW / ---
8.3 /
5.1
8.2 /
4.9
13.6 /
5.2
13.5 /
5.0
17.1 /
5.3
16.9 /
5.2
21.5 /
5.5
21.3 /
5.3
26.4 /
5.1
26.1 /
4.9
3.4 Sound power level dB(A) 53 55 55 58 59
3.5 Heating water flow with an internal pressure differential of m³/h / Pa
0.75 /
7000
1.4 /
24000
1.3 /
7000
2.3 /
22000
1.6 /
2600
2.8 /
7600
2.0 /
8000
3.7 /
24300
2.4 /
12500
4.5 /
36000
3.6 Cold water flow at an internal pressure differential of
(heat source) m³/h / Pa
2.0 /
6200
1.9 /
5600
3.3 /
19000
3.2 /
13000
4.0 /
12000
3.6 /
9500
5.0 /
20000
4.8 /
17900
7.0 /
16000
6.7 /
14900
3.7 Refrigerant; total filling weight type / kg R407C / 1.7 R407C / 1.6 R407C / 3.5 R407C / 3.2 R407C / 4.5
4 Dimensions, connections and weight
4.1 Device dimensions without connections
2
H x W x L mm
2. Note that additional space is required for pipe connections, operation and maintenance.
1445 x 650 x
575
1445 x 650 x
575
1445 x 650 x
575
1445 x 650 x
575
1445 x 650 x
575
4.2 Device connections to heating system Inch
Thread 1¼"
external
Thread 1¼"
external
Thread 1¼"
external
Thread 1¼"
external
Thread 1¼"
external
4.3 Device connections to heat source Inch
Thread 1¼"
external
Thread 1¼"
external
Thread 1½" a Thread 1½" a Thread 1½" a
4.4 Weight of the transportable unit(s) incl. packing kg 156 168 187 189 259
5 Electrical Connection
5.1 Nominal voltage; fuse protection V / A 400 / 16 400 / 16 400 / 16 400 / 20 400 / 20
5.2 Nominal power consumption
1
W10 W35 kW
1.62 1.68 2.64 2.72 3.21 3.27 3.93 4.02 5.15 5.29
5.3 Starting current with soft starter A
30 (without
SS)
26 28 27 29
5.4 Nominal current W10 W35 / cos ϕ A / ---
2.9 /
0.8
3.03 /
0.8
4.8 /
0.8
4.91 /
0.8
5.8 /
0.8
5.90 /
0.8
7.0 /
0.8
7.25 /
0.8
9.4 /
0.8
9.54 /
0.8
6 Complies with the European safety regulations
3
3. See CE declaration of conformity
3333
7 Additional model features
7.1 Water in device protected against freezing
4
4. The heat circulating pump and the heat pump controller must always be ready for operation.
Yes Yes Yes Yes Yes
7.2 Performance levels 1 1 1 1 1
7.3 Controller internal/external Internal Internal Internal Internal Internal