Installation manual

24
2.3.3
2.3.3 Installation on a wall
Fig. 2.13: Wall installation (LIK 8TE / LI 9TE see Chap. 2.2.5 on p. 19)
Table 2.7: Table of dimensions for installation on a wall
NOTE
Either a light well or a rain guard should be used for the air outlet to avoid
shorting the air circuit.
2.4 Air-to-Water Heat Pumps for Outdoor Installation
Costs for outdoor installation
Frost-free established foundation
Laying insulating heating pipes for flow and return flow in the
ground
Laying electrical connecting and main cables in the ground.
Wall openings for connecting pipes
Condensate outflow (frost-free)
Set-up
Heat pumps for outdoor installation are equipped with specially
coated steel and are thereby weatherproof.
The device should always be installed on a permanently even
and horizontal surface. Frost-free paving slabs or foundations
are suitable as a base. The entire frame should lie directly on the
ground to ensure a good soundproof seal and to prevent the
water-bearing components from becoming too cold. If there are
any gaps, these should be sealed with weatherproof insulating
material.
Fig. 2.14: Example for the foundation plan of a heat pump with 4 lawn edging
stones and 4 paving slabs
Minimum clearances
It must be possible to carry out maintenance work without
hindrance. This can be ensured by maintaining a clearance of
1.2 m to thick walls.
Sound insulation measures
The lowest noise emissions are achieved if, from the air outlet
side at a surrounding distance of 3-5 meters, there is no sound
reflection through sound-proof surfaces (i.e. facade).
Additionally, the foundation can be covered up to the height of
the covering panels with sound-absorbing material (i.e. bark
mulch).
Noise emissions from the heat pumps depend on the respective
sound power levels and the installation conditions. Please refer
to Chap. 5 on p. 144 for more detailed information about the
interrelationship between the factors influencing acoustic
emissions, sound propagation and acoustic immissions.
Shorting of the air circuit
When installing the heat pump, please keep in mind that the air
cooled by the extraction of heat is blown out freely. For
installation close to a wall, the air outlet cannot face in the wall's
direction.
Installation in a hollow or in an inner courtyard is not permitted
because cooled air collects at ground level and is drawn in again
by the heat pump during lengthy operation.
Fig. 2.15: Minimum clearances for maintenance work
&RQGHQVDWHRXWIORZ
/LJKWZHOO
%HORZJURXQGOHYHO
6HDOLQJFROODU
$FFHVVRULHV
2SHUDWLQJVLGH
'LUHFWLRQRIDLUIORZ
%


(



%
5DLQJXDUG
$FFHVVRULHV
$ERYH
JURXQGOHYHO
Type Heat Pump B (in mm) E (in mm)
600 LI 11ME / LI 11TE 650 852
700 LI 16TE / LI 20TE 745 852
800
LI 24TE - LI 28TE /
LIH 22TE - LIH 26TE
820 1002