Installation manual
www.dimplex.de 29
Air-to-Water Heat Pumps 2.6.2
2.6.2 Low-temperature heat pumps with the air circuit diverted at a 90° angle LI 9TE
Device information for air-to-water heat pumps for heating purposes
1 Type and order code
LI 9TE
2Design
2.1 Degree of protection according to EN 60 529 for compact devices and
heating components
IP21
2.2 Installation location Indoors
3 Performance data
3.1 Operating temperature limits:
Heating water flow/return flow °C / °C up to 58 / above 18
Air °C -25 to +35
3.2 Temperature spread of heating water (flow/return flow) at A7 / W35 K 10.0 5.0
3.3 Heat output / COP at A-7 / W35
1
kW / ---
1. This data indicates the size and capacity of the system according to EN 255 or EN14511. For an analysis of the economic and energy efficiency of the system, other parameters,
particularly the defrosting capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning:
2 °C external air temperature and 55 °C heating water flow temperature.
5.8 / 2.7 5.5 / 2.6
at A-7 / W45
1
kW / ---
5,4 / 2,1
at A2 / W35
1
kW / ---
7.5 / 3.3 7.4 / 3.2
at A7 / W35
1
kW / ---
9.3 / 3.9 9.2 / 3.8
at A7 / W45
1
kW / ---
8.8 / 3.2
at A10 / W35
1
kW / ---
9.8 / 4.1 9.7 / 4.0
3.4 Sound power level device / outdoors dB(A) 53 / 60
3.5 Sound pressure level at a distance of 1 m (indoors) dB(A) 48.0
3.6 Heating water flow with an internal pressure differential of m³/h / Pa 0.8 / 2700 1.6 / 11900
3.7 Air flow with an external static pressure differential of m³/h / Pa 2500 / 20
3.8 Refrigerant; total filling weight type / kg R404A / 1.9
3.9 Max. output of electric heating element (2nd heat generator) kW 6.0
4 Dimensions, connections and weight
4.1 Device dimensions H x W x L cm 125 x 75 x 68
4.2 Device connections to heating system Inch Thread 1'' external
4.3 Air duct inlet and outlet (min. internal dimensions) L x W cm 44 x 44
4.4 Weight of the transportable unit(s) incl. packing kg 177
5 Electrical connection
5.1 Nominal voltage; fuse protection V / A 400 / 25
5.2 Nominal power consumption
1
A2 W35 kW
2.27 2.33
5.3 Starting current with soft starter A 19,5
5.4 Nominal current A2 W35 / cosϕ A / --- 4.1 / 0.8 4.2 / 0.8
6 Complies with the European safety regulations
2
2. See CE declaration of conformity
7 Additional model features
7.1 Defrosting Automatic
Type of defrosting Reverse circulation
Defrosting tray included Yes (heated)
7.2 Heating water in device protected against icing
3
3. The heat circulating pump and the heat pump controller must always be ready for operation.
Yes
7.3 Performance levels 1
7.4 Controller internal/external Internal