2.7.1 Low-temperature heat pumps LA 11MS to LA 16MS
Device information for air-to-water heat pumps for heating purposes
1 Type and order code
LA 11MS LA 16MS
2Design
2.1 Degree of protection according to EN 60 529 for compact devices and
heating components
IP24 IP24
2.2 Installation location Outdoors Outdoors
3 Performance data
3.1 Operating temperature limits:
Heating water flow/return flow
1
°C / °C
1. See operating limits diagram
up to 55 / above 18 up to 55 / above 18
Air °C -20 to +35 -20 to +35
3.2 Temperature spread of heating water at A2 / W35 7.8 7.8
Heat output / COP at A-7 / W35
2
kW / ---
2. This data indicates the size and capacity of the system according to EN 255 or EN14511. For an analysis of the economic and energy efficiency of the system, other parameters,
such as, in particular, the defrosting capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following
meaning: external air temperature 2 °C and heating water flow temperature 55 °C.
7.6 / 2.9 9.8 / 2.6
at A2 / W35
2
kW / ---
9.1 / 3.4 12.7 / 3.2
at A2 / W50
2
kW / ---
9.0 / 2.5 12.2 / 2.4
at A7 / W35
2
kW / ---
10.9 / 4.1 15.4 / 3.7
at A10 / W35
2
kW / ---
12.0 / 4.6 16.1 / 3.8
3.3 Sound power level dB(A) 63 64
3.4 Sound pressure level at a distance of 10 m (air outlet side) dB(A) 33 34
3.5 Heating water flow with an internal pressure differential of m³/h / Pa 1.0 / 3000 1.4 / 4500
3.6 Air flow m³/h / Pa 2500 4000
3.7 Refrigerant; total filling weight type / kg R404A / 2.5 R404A / 3.1
4 Dimensions, connections and weight
4.1 Device dimensions H x W x L cm 136 x 136 x 85 157 x 155 x 85
4.2 Device connections to heating system Inch Thread 1'' external Thread 1'' external
4.3 Weight of the transportable unit(s) incl. packing kg 219 264
5 Electrical connection
5.1 Nominal voltage; fuse protection V / A 230 / 25 230 / 32
5.2 Nominal power consumption
2
A2 W35 kW
2.65 3.95
5.3 Starting current with soft starter A 38 45
5.4 Nominal current A2 W35 / cosϕ A / --- 14.4 / 0.8 21.5
6 Complies with the European safety regulations
3
3. See CE declaration of conformity
3
7 Additional model features
7.1 Defrosting Automatic Automatic
Type of defrosting Reverse circulation Reverse circulation
Defrosting tray included Yes (heated) Yes (heated)
7.2 Heating water in device protected against icing
4
4. The heat circulating pump and the heat pump controller must always be ready for operation.
Yes Yes
7.3 Performance levels 1 1
7.4 Controller internal/external External External