Installation manual

34
2.8
2.8 Device Information for Air-to-Water Heat Pumps for Outdoor
Installation (3-phase, 400 V AC)
2.8.1 Low-temperature heat pumps LA 8AS to LA 16AS
Device information for air-to-water heat pumps for heating purposes
1 Type and order code
LA 8AS LA 11AS LA 16AS
2Design
2.1 Degree of protection according to EN 60 529 for compact devices and
heating components
IP24 IP24 IP24
2.2 Installation location Outdoors Outdoors Outdoors
3 Performance data
3.1 Operating temperature limits:
3.2 Heating water flow/return flow
1
°C / °C
1. See operating limits diagram
up to 55 / above 18 up to 55 / above 18 up to 55 / above 18
3.3 Air °C -25 to +35 -25 to +35 -25 to +35
3.4 Temperature spread of heating water (flow/return flow) at A2 / W35 7.1 7.5 7.5
3.5 Heat output / COP at A-7 / W35
2
kW / ---
2. This data indicates the size and capacity of the system according to EN 255 or EN14511. For an analysis of the economic and energy efficiency of the system, other parameters,
particularly the defrosting capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning:
2 °C external air temperature and 55 °C heating water flow temperature.
5.1 / 2.5 7.1 / 2.9 9.8 / 2.6
at A2 / W35
2
kW / ---
6.6 / 3.1 8.8 / 3.2 12.2 / 3.2
at A2 / W50
2
kW / ---
6.2 / 2.4 8.5 / 2.5 11.5 / 2.4
at A7 / W35
2
kW / ---
8.3 / 3.7 11.3 / 3.8 15.4 / 3.7
at A10 / W35
2
kW / ---
8.8 / 3.8 12.2 / 4.1 16.1 / 3.8
3.6 Sound power level dB(A) 62 63 64
3.7 Sound pressure level at a distance of 10 m (air outlet side) dB(A) 32 33 34
3.8 Heating water flow with an internal pressure differential of m³/h / Pa 0.8 / 2700 1.0 / 3000 1.4 / 4500
3.9 Air flow m³/h / Pa 2500 2500 4000
3.10 Refrigerant; total filling weight type / kg R404A / 1.9 R404A / 2.5 R404A / 3.1
4 Dimensions, connections and weight
4.1 Device dimensions H x W x L cm 128 x 75 x 65 136 x 136 x 85 157 x 155 x 85
4.2 Device connections to heating system Inch Thread 1'' external Thread 1'' external Thread 1'' external
4.3 Weight of the transportable unit(s) incl. packing kg 166 219 264
5 Electrical connection
5.1 Nominal voltage; fuse protection V / A 400 / 16 400 / 16 400 / 20
5.2 Nominal power consumption
2
A2 W35 kW
2.1 2.74 3.81
5.3 Starting current with soft starter A 19.5 23 25
5.4 Nominal current A2 W35 / cosϕ A / --- 3.8 / 0.8 4.9 / 0.8 6.9 / 0.8
6 Complies with the European safety regulations
3
3. See CE declaration of conformity
3 3
7 Additional model features
7.1 Defrosting Automatic Automatic Automatic
Type of defrosting Reverse circulation Reverse circulation Reverse circulation
Defrosting tray included Yes (heated) Yes (heated) Yes (heated)
7.2 Heating water in device protected against icing
4
4. The heat circulating pump and the heat pump controller must always be ready for operation.
Yes Yes Yes
7.3 Performance levels 1 1 1
7.4 Controller internal/external External External External