Operating instructions

36
730.138 | 08.12
EN
System 14: 1 collector array – 1 storage tank
1 swimming pool in stand-alone operation
with external heat exchanger
intelligent valve control
Description of the solar function: When the switch-on temperature
difference between the collector array A1 (T1) and the storage tank B1
(T2) or the swimming pool C1 (T3) is reached, the solar circuit pump R1
is switched on and the switching valve R2 is set to the correct position
depending on the storage tank / swimming pool to be loaded. Either
storage tank B1 or the swimming pool C1 is loaded, according to the
priority control (chapter 7.5 "Storage tank priority"), until either the rel-
evant switch-off temperature difference between the collector array A1
(T1) and the storage tank B1 (T2) or swimming pool C1 (T3) is reached,
or a safety limit is reached. The swimming pool pump is controlled exter-
nally.
NOTE
When no voltage is on the system, the switching valve R2 must be set
to storage tank B1.
Loading strategy of solar circuit pump R1 for storage tank:
In the
factory, temperature differential control is chosen as the loading strat-
egy for the storage tank B1. It can be adjusted or changed to target
temperature control using the "Parameters" menu (chapter 7.4 "Param-
eters").
Loading strategy of solar circuit pump R1 for swimming pool:
In
the factory, the loading strategy for the swimming pool C1 is set to
temperature differential control. This cannot be altered.
Activating the system: see chapter 7.2. "Selecting a system".
Terminal layout
N L N
R1
N
n.c.
n.c.
X
L
L
n.c.
1
2
3
4
5
T1
T2
T3
D1
R2
R1
230 V~
115 V~
A1
B1
C1
T3
n.c.
n.c.
T2
T1
R1
R2
R2
n.c.
n.c.
F1
Display: 2.2.3Display: 2.2.3
A1: collector array
B1: storage tank
C1: swimming pool
D1: wire bridge
F1: external heat exchanger
R1: solar circuit pump
R2: switching valve
T1: collector sensor
T2: lower area of storage tank
T3: sensor swimming pool
A1: collector array
B1: storage tank
C1: swimming pool
D1: wire bridge
F1: external heat exchanger
R1: solar circuit pump
R2: switching valve
T1: collector sensor
T2: lower area of storage tank
T3: sensor swimming pool