10.1 Causes of problems
Controller does not appear to function at all:
Secondary symptoms Possible cause Procedure
Display shows nothing
No display illumination
Controller power supply is
interrupted
Check the controller power cable
Check the fuse for the power supply
Check the fuse at the controller
(replacement fuse is located in the
case)
The solar pump does not operate, despite the fact that the switch-on conditions
are satisfied:
Secondary symptoms Possible cause Procedure
The pump symbol in the
display rotates
Pump power supply is
interrupted
Pump has seized up
Check the pump power cable
Check the fuse in the controller
(replacement fuse is located in the
case)
Get the pump working again,
replace if necessary
The pump symbol in the
display does not rotate
The maximum storage
tank temperature has
been reached
The maximum collector
temperature has been
reached
In multi storage tank
systems: the system has
stopped due to a priority
test
The minimum collector
temperature has not
been reached
The maximum loading
temperature has been
reached
Stagnation reduction
activated
Storage tank deactivated
No fault
The pump symbol in the
display does not rotate
The display illumination
is red
A tool symbol flashes in
the display
The operating switch is set
to manual operation and
the pump output is set to
"off"
Set the operating switch to auto-
matic operation
The pump symbol in the
display does not rotate
The display illumination
flashes red
Short circuit or interruption
of a temperature sensor
On the controller, request the
current values from all connected
temperature sensors
Check all defective sensors and/or
sensor cable