Operating instructions

60
730.138 | 08.12
EN
The solar pump operates, despite the fact that the switch-on condition is not
fulfilled:
Secondary symptoms Possible cause Procedure
The pump symbol in
the display rotates
The interval function is acti-
vated
The holiday function is acti-
vated
The frost protection function is
activated
Blockage protection is acti-
vated
No fault
Deactivate the relevant function, if
necessary
Symbol rotates
Display has a red
background
Tool symbol is visible
on the display
The operating switch is set to
manual operation and the pump
output is set to "on"
Set the operating switch to auto-
matic operation
Solar pump is operating, activation condition is fulfilled, nevertheless, no heat
transport in the solar circuit (no "fluid circulation"):
Secondary symptoms Possible cause Procedure
The pump symbol in
the display rotates
Air is in the solar circuit
The isolating valve is closed
Limescale/contamination on
solar circuit
Check the solar circuit for air
Check the isolating valve
Flush/clean the solar circuit
Solar pump shows cycle behaviour
Secondary symptoms Possible cause Procedure
Temperature difference too
small
Collector sensor incorrectly
positioned
Adjust temperature difference in the
Parameters menu
Check the collector sensor
10.2 Pt1000 temperature sensor values
A potentially defective sensor can be checked using an ohmmeter To do this, the sensor must be discon-
nected, its resistance measured, and the value compared with the figures in the table below. Small devia-
tions are acceptable.
Temperature [°C] -30 -20 -10 0 10 20 30 40 50 60 70
Resistance [Ω] 882 922 961 1000 1039 1078 1117 1155 1194 1232 1271
Temperature [°C] 80 90 100 110 120 130 140 150 160 170 180
Resistance [Ω] 1309 1347 1385 1423 1461 1498 1536 1573 1611 1648 1685