Technical data

1111..00 SSEERRVVIICCEE MMOODDEE
2266
© Dimple
x Boiler
s 2008
NNOOTTEE::
Service Mode automatically stops after 10 minutes
and the boiler returns to normal operation.
1. Turn the CH knob fully clockwise - Note the knob will turn
past the maximum temperature mark (Fig. 45).
2. The CH light will flash continuously - the boiler is now
running at minimum rate.
1. Set the boiler into Service Mode at Minimum Rate.
2. Whilst in Service Mode at Min Rate, turn the CH knob to 12
‘O’ clock position and then back to fully clockwise (past the
maximum temperature indicator) within 3 seconds. The boiler
will now run at maximum gas rate for 10 minutes.
3. To exit Service Mode, turn the CH knob anti-clockwise to
the temperature previously set by the customer. The CH light
will now stop flashing.
1111..11 TTOO SSEETT TTHHEE BBOOIILLEERR AATT MMIINNIIMMUUMM GGAASS RRAATTEE
1111..22 TTOO SSEETT TTHHEE BBOOIILLEERR AATT MMAAXXIIMMUUMM GGAASS RRAATTEE
FFiigg.. 4455 FFiigg.. 4466