Operating instructions

E-6
English
5
5 Preconfiguring the Heat Pump Heating System
The preconfiguration informs the controller about which
components are connected to the heat pump heating system.
Preconfiguration must be carried out before the system-specific
settings in order to show or hide menu items (dynamic menus).
The following table shows not only the menu structure and
explanations in the right-hand column, but also the
corresponding setting ranges. Values in bold print indicate the
factory settings.
The factory settings in the “Preconfiguration” menu correspond
to the integration diagram for a mono energy heat pump
(normally an air-to-water heat pump) with 1 compressor and a
heating circuit, without DHW heating using the heat pump.
5.1 Menu
You can access the preconfiguration menu by:
Simultaneously pressing (approx. 5 seconds) the button
combination (ESC) and (MENU).
Exit the preconfiguration via the (ESC) button.
Abbreviations:
The following presettings must be carried out:
HP Heat pump
AW HP Air-to-water heat pump
BW HP Brine-to-water heat pump
WW HP Water-to-water heat pump

Preconfiguration of all system components for
dynamic menu structuring
Setting range Display
  
Has the system got a heating circuit 2 with a
controllable mixer?
No
Yes
Always

Is active cooling implemented in the system? No
Yes
Always
   
Is DHW heating carried out by the heat pump? No
Yes
Always
  

 
Is a sensor or thermostat used to regulate DHW
heating?
Sensor
Thermostat
Domestic hot water
preparation
 
Is a flange heater used in the hot water cylinder
for thermal disinfection?
No
Yes
Domestic hot water
preparation sensor