Configuring the Heat Pump Heating System 6.1
6 Configuring the Heat Pump Heating System
The menus for “Outputs”, “Inputs” and “Special functions” as well
as the extended setting menu can be set at the configuration
level. The extended menu level for technicians is called by
simultaneously pressing the button combination (MENUE) and
(ENTER ) (for approx. 5 seconds)
Select the desired menu item with the arrow buttons and confirm
with the ENTER button ().
6.1 Settings
Depending on the system configuration, the full “Settings” menu
contains the following inquiries:

System-specific parameters
Setting range Display

Menu for setting the time. International 24 h
display
Always

Level for setting operating modes Always
 
Selects the operating mode
It is also possible to make changes directly
using the modus button.
Cooling
Summer
Auto
Party
Vacation
HG 2
Always
 
  
Duration of party mode in hours
After the set period has elapsed, the system
returns automatically back to automatic
operation again.
0
... 4 ...
72
Always
 
  
Duration of vacation mode in days
After the set period has elapsed, the system
returns automatically to automatic operation
again.
0
... 15 ...
150
Always
  
Settings for heating circuit 1 Always
  
 
The following heating regulation options are
available for heating circuit 1:
* Return temperature regulation based on the
external temperature and the set heating curve
* Return temperature regulation via a fixed-
setpoint (horizontal heating characteristic
curve)
* Return temperature regulation based on the
room temperature in a reference room
External
temperature
Fixed-setpoint
Room temperature
Always
  
   
The heating curve end point should be set
according to the design of the heating system.
This should be done by entering the maximum
return temperature, which is the product of the
maximum calculated flow temperature minus
the temperature difference in the heating
system (spread).
20 °C
... 30 °C ...
70 °C
External temperature
  

Sets the desired return set temperature when
fixed-setpoint regulation is selected
15 °C
... 40 °C ...
60 °C
Fixed-setpoint
  
  
Sets the desired room set temperature when
room temperature regulation is selected
15 °C
... 20 °C ...
30 °C
Room regulation
  

Sets the minimum return temperature when
room temperature regulation is selected
15 °C
... 20 °C ...
30 °C
Always