INSTALLATION INSTRUCTIONS FOR SELF-CONTAINED PACKAGE AIR CONDITIONERS AND HEAT PUMP UNITS *PC/*PH 14 SEER “H” SERIES WITH R-410A RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION. All information contained herein is subject to change without notice. ATTENTION INSTALLING PERSONNEL Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During installation or repair, caution is to be observed.
TO THE INSTALLER ........................................................ 2 ELECTRIC HEAT INSTALLATION & ADJUSTMENT ... 11 SHIPPING INSPECTION .............................................. 2 MAINTENANCE .............................................................. 12 Checking Product Received ......................................... 2 Message to the Homeowner ........................................ 3 SERVICE ........................................................................
Message to the Homeowner These instructions are addressed primarily to the installer; however, useful maintenance information is included and should be kept, after installation, for future reference. WARNING TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO NOT USE THIS UNIT IF ANY PART HAS BEEN UNDER WATER.
EPA Regulations Close to the wall application assures free, unobstructed air to the other two sides. In more confined application spaces, such as corners provide a minimum 10” clearance on all air inlet sides. Allow 18” minimum for service access to the compressor compartment and controls. The top of the unit should be completely unobstructed. If units are to be located under an overhang, there should be a minimum of 36” clearance and provisions made to deflect the warm discharge air out from the overhang.
3. 4. To ensure proper condensate drainage, unit must be installed in a level position. Consideration should also be given to shade, appearance and noise. Specification Sheets for Dimension details). The SQRPCH101 has 14" duct collar on supply and 16" duct collar (equivalent diameter, opening is oval) on the return. The SQRPCH102 and SQRPCH103 have 14" duct collar on supply and 18" duct collar (equivalent diameter, opening is oval) on the return.
On ductwork exposed to outside air conditions of temperature and humidity, use an insulation with a good K factor, and a vapor barrier. Industry practices should be followed. Balancing dampers are recommended for each branch duct in the supply system. Ductwork should be properly supported from the unit. NOTE: Proper sealing of all duct work and air handling compartments is extremely important to overall unit efficiency.
b. Heat Pumps- Connect 24V wires from the thermostat to the corresponding wires in the control box using No. 18AWG as follows: TERMINAL Red Green Orange W hite Brown Yellow C (Blue) THERMOSTAT R (24V) G (Fan) O (Rev. Valve) W 1 (Heat, 2nd)* W 2 (Heat 3rd)* Y (Cool) C (Common) *Optional field installed heat connections 4. Turn the fan switch to the “ON” position. The blower should operate after a 10 second delay. 5. Turn the fan switch to “Auto” position.
15. If checking the unit in the wintertime, when the outdoor coil is cold enough to actuate the defrost control, observe at least one defrost cycle to make sure the unit defrosts completely. The foregoing “Start-up Procedure and Check List” is recommended to serve as an indication that the unit will operate normally. COMPONENTS Final System Checks 1. Contactor - This control is activated (closed) by the room thermostat for both heating and cooling.
5. Contactor Relay - This control is activated by the thermostat (24V coil) and supplies power to the contactor. 6. Defrost Control - The Defrost control provides time/ temperature initiation and termination of the defrost cycle. When a Defrost cycle is initiated, the defrost control shifts the reversing valve to “cooling” mode, stops the outdoor fan and brings on supplemental heat. Normally, a Defrost cycle will take only 2-3 minutes unless system is low on charge or outdoor conditions are severe.
temperature, a twelve minute override interrupts the unit’s defrost period. utilized, the speed tap can be changed. Never run CFM below 350 CFM per ton, evaporator freezing or poor unit performance is possible. SUGGESTED FIELD TESTING/TROUBLE SHOOTING ADJUSTING SPEED TAP 1. Run unit in the heating mode (room thermostat calling for heat). 2. Check unit for proper charge. Note: Bands of frost on the condenser coil indicate low refrigerant charge. 3. Shut off power to unit. 4.
SATURATED SUCTION PRESSURE TEMPERATURE CHART SATURATED LIQUID PRESSURE TEMPERATURE CHART SATURATED SUCTION SUCTION PRESSURE TEMPERATURE ºF SATURATED LIQUID LIQUID PRESSURE TEMPERATURE ºF *PC Design superheat @ 95 °F outdoor ambient temperature Models # Superheat ± 2°F *PC1424H41 10 *PC1430H41 10 6 PSIG R-410A PSIG R-410A *PC1436H41 50 1 200 70 *PC1442H41 7 52 3 210 73 *PC1448H41 12 54 4 220 76 *PC1460H41 6 56 6 225 78 58 7 235 80 60 8 245 83 *PH 62 10 255 85
SERVICE THE FOLLOWING INFORMATION IS FOR USE BY QUALIFIED SERVICE AGENCY ONLY: OTHERS SHOULD NOT ATTEMPT TO SERVICE THIS EQUIPMENT. Common Causes of Unsatisfactory Operation of Heat Pump on the Heating Cycle. Inadequate Air Volume Through Indoor Coil When a heat pump is in the heating cycle, the indoor coil is functioning as a condenser. The return air filter must always be clean, and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure, and high pressure cut out.
*PC/*PH14[24-36]H41 BLOWER PERFORMANCE *PC / *PH14[24-36]H41 BLOWER PERFORMANCE *PC1424H41** Model T1 T2 / T3 *PH1424H41** T4 / T5 T1 T2 / T3 *PC1430H41** T4 / T5 T1 T2 / T3 *PH1430H41** T4 / T5 T1 T2 / T3 *PC1436H41** *PH1436H41** T4 / T5 T1 T2 / T3 T4 / T5 E.S.P. (In. of H2 O) Volts Speed 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.
*PC/*PH14[42-60]**H41 BLOWER PERFORMANCE *PC1448H41 E* *PH1448H41 E* *PC1442H41 E* *PH1460H41** *PC1460H41** *PC1448H41** *PH1448H41** *PH1442H41** *PC1442H41** Model T1 T2 / T3 T4 / T5 T1 T2 / T3 T4 / T5 T1 T2 / T3 T4 / T5 E.S.P. (In. of H2 O) Volts Speed 230 230 230 230 230 230 230 230 230 T1 230 T2 / T3 230 T4 / T5 230 T1 230 T2 / T3 230 T4 / T5 230 T1 230 T2/T3 230 T4/T5 230 T1 230 T2/T3 230 T4/T5 230 CFM 0.1 1165 0.2 1122 0.3 1080 0.4 1037 0.5 995 0.6 953 0.
TROUBLESHOOTING CHART WARNING HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE , PERSONAL INJURY OR DEATH . POSSIBLE CAUSE SYMPTOM High head - low suction High head - high or normal suction Low head - high suction Unit will not run a. a. b. c. a. b. c.
PACKAGE UNITS - HEAT PUMP AND AC UNITS HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS We strongly recommend a bi-annual maintenance checkup be performed by a qualified service agency before the heating and cooling seasons begin. aluminum tube residential cooling coils. An alternate cleaning method is to use one of the products listed in the technical publication TP-109 (shipped in the literature bag with the unit) to clean the coils.
Start-up Checklist *Store in job file Air Conditioning & Heating Date: ___________________________________ Location: __________________________________________ Model Number: ___________________________________ __________________________________________ Serial Number: ___________________________________ __________________________________________ Technician: ___________________________________ Unit #: __________________________________________ Pre Start-Up (Check each item as completed) Verify al
Start-up Checklist Air Conditioning & Heating Start-Up (Insert the values as each item is completed.) ELECTRICAL Supply Voltage L1 - L2 L2 - L3 L3 - L1 Circuit 1 Compressor Amps L1 L2 L3 Circuit 2 Compressor Amps L1 L2 L3 Blower Amps L1 L2 L3 Condenser Fan Amps Fan 1 Fan 2 Fan 3 BLOWER EXTERNAL STATIC PRESSURE Return Air Static Pressure IN. W.C. Supply Air Static Pressure IN. W.C. Total External Static Pressure IN. W.C.
THIS PAGE LEFT INTENTIONALLY BLANK 19
Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com or www.amana-hac.com © 2010 - 2015 Goodman Manufacturing Company, L.P.