Instruction manual

Instruction Manual
D200354X012
4200 Transmitters
July 2013
21
Table 9. Transmitter and Position Switch Conditions (also see figure 7)
FOR ROTARY ACTUATORS
Type
Transmitter
Action
Actuator Style Actuator Stem Travel
Input Potentiometer
Rotation
(1)
Transmitter
Current Output,
Milliampere
Set Position Switch
4210
Direct
A,D
Down CW 20 Hi
Up CCW 4 Lo
B,C
Up CW 20 Hi
Down CCW 4 Lo
Reverse
A,D
Up CCW 20 Hi
Down CW 4 Lo
B,C
Down CCW 20 Hi
Up CW 4 Lo
4212
Direct
A,D
Down CW
N/A
Hi
Up CCW Lo
B,C
Up CW Hi
Down CCW Lo
Reverse Not available for position switches without transmitter
4215
Direct
A,D
Down CW 20 Hi
Up CCW 4 Lo
B,C
Up CW 20 Hi
Down CCW 4 Lo
Reverse
A,D
Down CW 4 Hi
Up CCW 20 Lo
B,C
Up CW 4 Hi
Down CCW 20 Lo
4211 Not required for transmitter without position switches
FOR SLIDING‐STEM ACTUATORS
4210
4220
Direct - - -
Down CW 20 Hi
Up CCW 4 Lo
Reverse - - -
Up CCW 20 Hi
Down CW 4 Lo
4212
4222
Direct - - -
Down CW N/A Hi
Up CCW N/A Lo
Reverse Not available for position switches without transmitter
4215
Direct - - -
Down CW 20 Hi
Up CCW 4 Lo
Reverse - - -
Down CW 20 Hi
Up CCW 4 Lo
4211,4221 Not required for transmitter without position switches
1. Viewed from the potentiometer shaft end.
Test Equipment Required
The following test equipment is used in the calibration and maintenance of the instrument:
D Digital voltmeter (DVM) that measures voltages in the range of 0 to 30 volts DC with an accuracy of ±0.25 percent.
D Power supply capable of supplying 20 to 30 volts DC at 100 mA.
D Resistor, 250 ohms, 0.1%, 0.5 watt or greater.