Instruction manual
Instruction Manual
D200354X012
4200 Transmitters
July 2013
49
Figure 25. Fisher 4211 and 4221 FM Schematic
GE16019-B
NOTES:
1. THE INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC
CODE (NEC), NFPA 70, ARTICLE 504 AND ANSI/ISA RP12.6.
2. THE CLASS 1, DIV 2 APPLICATIONS MUST BE INSTALLED AS SPECIFIED IN NEC
ARTICLE 501‐4(B). EQUIPMENT AND FIELD WIRING IS NON‐INCENDIVE WHEN
CONNECTED TO APPROVED BARRIERS WITH ENTITY PARAMETERS.
3. LOOPS MUST BE CONNECTED ACCORDING TO THE BARRIER MANUFACTURER'S
INSTRUCTIONS.
4. MAXIMUM SAFE AREA VOLTAGE SHOULD NOT EXCEED 250 Vrms.
5. RESISTANCE BETWEEN BARRIER GROUND AND EARTH GROUND MUST BE LESS
THAN ONE OHM.
6. FOR ENTITY INSTALLATION (I.S. AND N.I.):
Vmax > Voc, or Vt Ci + Ccable < Ca
Imax > Isc, or It Li + Lcable < La
Pi > Po, or Pt
4211, 4221
Vmax = 30 VDC
Imax = 150 mA
Pi = 1.0 W
Ci = 18 nF
Li = 0 mH
FM APPROVED BARRIER
SEE NOTE 6
HAZARDOUS LOCATION NON-HAZARDOUS LOCATION
I.S. CLASS I,II,III DIV 1, GROUPS A,B,C,D,E,F,G
N.I. CLASS I, DIV 2, GROUPS A,B,C,D
THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS CONSIDERED
TO CONSTITUTE A POTENTIAL RISK OF IGNTION BY IMPACT AND FRICTION.
AVOID IMPACT AND FRICTION DURING INSTALLATION AND USE TO
PREVENT RISK OF IGNTION.
WARNING