Instruction manual

Instruction Manual
D200354X012
4200 Transmitters
July 2013
8
ATEX
Special Conditions for Safe Use
Intrinsically Safe, Dust
4211 and 4221
This equipment is intrinsically safe and can be used in potentially explosive atmospheres.
The apparatus must only be connected to a certified associated intrinsically safe equipment and this combination
must be compatible as regards intrinsic safety rules.
The electrical parameters of the associated intrinsically safe equipment must not exceed any of the following values:
Uo 30 V, lo 150mA, Po 1W
Maximal ambient temperature: -40_C to +71_C.
Temperature classification is as follows: T5 at Ta + 40_C ; T4 at Ta + 71_C
The enclosure of the equipment must not be submitted to mechanical impact or friction.
Type n, Dust
4211 and 4221
No special conditions for safe use.
Flameproof, Dust
4210, 4211, 4212, 4215, 4220, 4221, and 4222
No special conditions for safe use.
Refer to table 7 for approval information, and figure 27 for typical ATEX/IECEx approval nameplates.
Table 7. Hazardous Area Classifications—ATEX
Certificate Type Certification Obtained Entity Rating Temperature Code Enclosure Rating
ATEX
4211, 4221
II 1 GD
Intrinsically Safe
Gas
Ex ia IIC T4/T5 Ga
Ui = 30 VDC
Ii = 150 mA
Pi = 1.0 W
Ci = 5 nF
Li = 0 mH
T4 (Tamb 71°C)
T5 (amb 40°C)
IP66
Dust
Ex ta IIIC T81°C Da (Tamb 71°C)
Ex ta IIIC T50°C Da (Tamb 40°C)
- - -
II 3 GD
Type n
Gas
Ex nA IIC T4 Gc
- - -
T4 (Tamb 71°C)
IP66
Dust
Ex tc IIIC T81°C Dc (Tamb 71°C)
- - -
4210, 4211, 4212,
4215, 4220, 4221,
4222
II 2 GD
Flameproof
Gas
Ex d IIC T5/T6 Gb IP66
- - -
T5 (Tamb 71°C)
T6 (Tamb 56°C)
IP66
Dust
Ex tb IIIC T72°C Db (Tamb -20°C to 56°C)
- - -