TITLE: SPA 1500 system
COMMISSIONING PROCEDURE
SIZE: A4 UED no:
DOC no: 96106-000-CP
FILE NAME: 96106-000-CP
Commissioning procedure.doc
COMMISSIONING PROCEDURE
FOR
SPA-1500 SYSTEM
1. CHECK THAT CABLING IS ACCORDING TO APPROVED DRAWINGS.
2. USE SPA-1501 AND 1593 UNIT TO ACCESS ZONE 1 TO 3 AND VERIFY AUDIO IN
THE CORRESPONDING SPEAKERS. ALSO VERIFY 24VDC VOLUME
OVERRIDE OUTPUT FOR ZONE 1-3(TERM.15/16,17/18,33/34) IF IN USE.
3. ACTIVATE ENTERTAINMENT IF INSTALLED AND VERIFY THAT IT’S
DISTRIBUTED TO THE SELECTED ZONE.(SWITCHES IN FRONT)
4. IF AN ALARMCARD IS INSTALLED TEST THAT BOTH ALARMS IS
DISTRIBUTED TO ALL ZONES AND CAN BE OVERRIDED BY THE
ACCESS PANEL(S) 1501 AND 1593. (USER1 TO USER 3 AND EXTERNAL INPUT)
CHECH PRIORITY AS FOLLOW:
• PRIO 1 = USER 1 (1501 OR 1593)
• PRIO 2 = USER 2
• PRIO 3 = USER 3
5. IF AN ALARMCARD OR DING-DONG CARD IS INSTALLED EACH
ANNOUNCEMENT COULD START WITH A PRETONE.
6. IF THE EXTERNAL INPUT IS IN USE, THEN CHECK THAT THE AUDIO
IS DISTRIBUTED TO THE PRESELECTED ZONES(DIPSWITCH S7 1-3)
7. IF EXTERNAL OUTPUT(AUDIO/KEY) IS IN USE, VERIFY AUDIO IS
PRESENT AT TERMINALS 100/101 REGARDLESS OF THE ZONE SELECTIONS.
KEY 1 AND 2 OUTPUT IS POTENSIAL FREE RELAY CONTACTS.