Operating instructions

- editing position
l [+] key:
- modify value of a parameter
l [ESC] key:
- interrupt input
- jump to the next higher menu
Note:
Approx. 10 minutes after the last pressing of a key, an
automatic reset to measured value indication is triggered. Any
values not conrmed with [OK] will not be saved.
6.2 Setup procedure
Setup encompasses mainly the selection of the application
and the adjustment of the measurement loop. Scaling the
measured value to the requested size and unit (possibly also
applying a linearization curve), as well as the adaptation of the
relay switching points, are additional settings. Further setup
steps might be, if necessary, the modication of the current
output characteristics or the setting of an integration time to
smooth the measured value.
For instruments with Ethernet interface, the instrument must be
provided with the host name and IP addr./Subnet mask. If
necessary, the e-mail/web server can also be congured with
PACTware.
VEGAMET 625 can process measured values of several
connected HART sensors. All measured values are trans-
mitted as digital HART signals on the same cable (bus).
Therefore an own, unique address (address range 1-15) must
be assigned rst of all to each connected sensor. This mode is
also called HART Multidrop mode. Addressing can be done
directly on each HART sensor via the respective adjustment
unit or an appropriate adjustment software. As an alternative,
the setting of the sensor address can be also carried out via
the VEGAMET menu under "Service Sensor address".
Note:
When addresses are being assigned, only one sensor with a
particular address must be connected on the bus. If this is not
the case, the sensor cannot be accessed and it is not possible
to assign an address.
After being switched on, VEGAMET 625 rst of all carries out a
short self-check. The following steps are carried out:
Set up
Set HART address
Switch on phase
18 VEGAMET 625 - Double channel Hart signal conditioning instrument
Setup with the integrated indicating and adjustment unit
28970-EN-050616