Operating instructions
Units of measurement 1
m(d)
▼
The following illustrations and examples relate to the min./max.
adjustment of a radar sensor.
Min. adjustment 1
0.00 %
≙
32.00 m(d)
9.245 m(d)
à With [OK] you prepare the percentage value for editing,
with [–>] you set the cursor to the requested position. Set
the requested percentage value with [+] and save with
[OK]. The cursor jumps now to the distance value.
à Enter now the appropriate distance value in m [m(d)]
(corresponding to the percentage value) for the empty
vessel (e.g. distance from the sensor to the vessel bottom).
à Save the settings with [OK] and move to "Max. adjustment"
with [–>].
Max. adjustment 1
100.00 %
≙
0.000 m(d)
0.489 m(d)
à As previously described, enter now the percentage value
for the max. adjustment and confirm with [OK].
à Enter now the appropriate distance value in m [m(d)]
(corresponding to the percentage value) for the full vessel.
Keep in mind that the max. level must be below the radar
antenna.
à Finally save your settings with [OK], the adjustment is
finished.
To suppress fluctuation in the measured value display, e.g.
caused by an agitated product surface, an integration time can
be set. This time can be between 0 and 999 seconds. Keep in
mind, that this setting will increase the reaction time of the
Meas. loop – Damping
VEGAMET 625 - Double channel H art signal conditioning instrument 23
Setup with the integrated indicating and adjustment unit
28970-EN-050616