Operating instructions

measurement and that the reaction to quick changes of the
measured value will be delayed. In general, a time of a few
seconds is sucient to smooth the measured value display.
Damping 1
1 s
à Enter the requested parameter via the appropriate keys
and save your settings with [OK].
A linearization is necessary for all vessels in which the vessel
volume does not increase linearly with the level, e.g. with a
cylindrical or spherical tank. Corresponding linearization
curves are preprogrammed for these vessels. They represent
the correlation between the level percentage and vessel
volume. By activating the appropriate curve, the volume
percentage of the vessel is displayed correctly. If the volume
should not be displayed in percent but e.g. in l or kg, a scaling
can be also set.
Linearization curve 1
linear
à Enter the requested parameter via the appropriate keys
and save your settings with [OK].
Scaling is the conversion of the measured value into a certain
parameter or measuring unit. Instead of the percentage value,
the volume can be displayed, e.g. in l. Indicating values
between max.-99999 and +99999 are possible.
Scaling: Unit 1
Mass
kg
à Enter the requested parameter via the appropriate keys
and save your settings with [OK].
Meas. loop Linearization
curve
Meas. loop Scaling
24 VEGAMET 625 - Double channel Hart signal conditioning instrument
Setup with the integrated indicating and adjustment unit