Operating instructions
In this menu item you can enter an unambiguous designation
for each measurement loop, e.g. the measurement loop name
or the tank or product designation. In digital systems and in the
documentation of larger plants, a unique designation should be
entered for exact identification of individual measuring sites.
Meas. loop TAG 1
TAG-No. 1
à Enter the requested parameter via the appropriate keys
and save your settings with [OK].
Under "Outputs" you will find the relay and current outputs.
With relay output, first of all the requested mode ("Overfill
protection" or "Dry running protection") must be selected.
Relay operating mode 1
Overfill protection
à Enter now the switching points for switching the relay on
and off. The parameter to which they refer can also be
selected.
Relay switching points 1
Basic meas. value:
Percent
▼
In the following window the reaction of the relay in case of
failure can be determined. Here you can define whether, in
case of failure, the switching condition of the relay remains
unchanged or the relay is switched off.
The characteristics of the current outputs can be set to
0 … 20 mA, 4 … 20 mA or inverted. The reaction in case of
failure can be also adapted to the requirements. The para-
meter to which they refer can also be selected.
Meas. loop – Meas. loop TAG
Meas. loop – Outputs – Relay
outputs
Meas. loop – Outputs – Cur-
rent outputs
VEGAMET 625 - Double channel H art signal conditioning instrument 25
Setup with the integrated indicating and adjustment unit
28970-EN-050616