Operating instructions
Note:
When addresses are being assigned, only one sensor with a
particular address must be connected on the bus. If this is not
the case, the sensor cannot be accessed and it is not possible
to assign an address.
Set the current HART address of the requested sensor in the
menu item "Previous address". The default setting of all
supplied VEGA sensors is always 00. After pushing the [–>]
key, you can assign the requested HART address in the range
of 01 – 15 in the menu "New address". Make sure that no
address is assigned twice.
Sensor address
New address:
01
In the menu item "Info" the following information is available:
l Sensor type and serial number
l Date of manufacture and software version
l Date of last change using PC
l Details of VEGAMET 625
l MAC address (with interface option Ethernet)
Additional adjustment and diagnostics options are available via
the Windows software PACTware™ and the suitable DTM.
Connection can be made via the interface converter VEGA-
CONNECT or RS232/Ethernet (depending on the instrument
version). Further information is available in chapter "Parameter
adjustment with PACTware™, in the online help of
PACTware™ or the DTM as well as in the operating
instructions manual "RS232/Ethernet connection".
Info
Further settings
VEGAMET 625 - Double channel H art signal conditioning instrument 27
Setup with the integrated indicating and adjustment unit