Operating instructions
2
4
3
1
Fig. 8: Connection of the modem via RS232
1 Analogue, ISDN or GSM modem with RS232 interface
2 RS232 modem connection cable (in the scope of delivery)
3 RS232 interface of VEGAMET 625
4 VEGAMET 625
With the Ethernet interface, VEGAMET 625 can be connected
directly to an existing PC network. Any standard patch cable
can be used. When connecting a VEGAMET 625 directly to
the PC, a cross-over cable must be used. To reduce EMC
interference, you should mount the supplied ferrite bead on the
Ethernet connection cable. Each VEGAMET 625 then gets its
own IP address under which it can be accessed from
anywhere in the network. The parameter adjustment of the
instrument via PACTware™ can be carried out from any PC.
The measured values can be made available to individual
users within the company network as HTML chart. Alternativ-
ely, independent, time or event-controlled transmission of
measured values via e-mail is also possible.
For more comprehensive requirements, we recommend using
the software " Visual VEGA " for measured value enquiry and
visualisation.
Note:
To adjust with PACTware™ and DTM, a suitable IP address
must be available in the instrument. Each instrument is preset
to address 192.168.200.200. Enter the address and subnet
mask corresponding to your network directly via the keyboard.
Briefly interrupt the power supply, then the instrument is
accessible via its IP address everywhere in the network. In
addition, this information must be entered in the DTM (see
chapter "Parameter adjustment with PACTware™").
Connection of the PC via
Ethernet
VEGAMET 625 - Double channel H art signal conditioning instrument 39
Setup with PACTware™