Operating instructions
PACTware /
VE
G
A-DT
M
TM
2
4
3
1
Fig. 9: Connection of the PC via Ethernet
1 Ethernet interface of the PC
2 Ethernet connection cable (patch cable)
3 Ethernet interface of VEGAMET 625
4 VEGAMET 625
7.2 Parameter adjustment with PACTware™
VEGAMET 625 signal conditioning instrument can be operated
via a Windows PC. You will need the configuration software
PACTware™ and a suitable instrument driver (DTM) acc. to
the FDT standard. In addition, the VEGA DTMs can be
integrated in other frame applications acc. to FDT standard.
For connection either the interface converter VEGACONNECT
or one of the offered interfaces (Ethernet/RS232) in VEGAMET
625 is required. Not only VEGAMET 625 itself, but also
connected VEGA HART sensors can be accessed.
When connecting via Ethernet, VEGAMET 625 must be
provided with a suitable IP address and subnet mask. This
information must be entered additionally in the DTM. Click in
the project window with the right mouse key to the VEGA
Ethernet DTM and choose "Add. functions – Modify DTM
addresses").
Note:
Connection of VEGACONNECT or a HART modem directly to
the 4 … 20 mA sensor cable is not possible.
All currently available VEGA DTMs are combined under the
name "DTM Collection" with the current PACTware™ version
on CD. They are available from the responsible VEGA agency
40 VEGAMET 625 - Double channel Hart signal conditioning instrument
Setup with PACTware™