Operating instructions
? E030
l Invalid measured value
à Check sensor parameter adjustment
? E034
l EEPROM defective
à Carry out a reset
à Return instrument for repair
? E035
l EEPROM CRC-error
à Carry out a reset
à Return instrument for repair
? E036
l Instrument software not executable (during software
update or after failed update)
à wait until software update is finished
à Carry out another software update
? E053
l Sensor measuring range not read correctly
à HART communication error: Check sensor cable and
screening
? E062
l Pulse priority too small
à Increase under "Output" th entry "Pulse output all" so
that max. one pulse per second is outputted.
48 VEGAMET 625 - Double channel Hart signal conditioning instrument
Maintenance and fault rectification