Operating instructions

19
6 Setup with the integrated display and adjustment unit
VEGAMET 625 • Double channel HART
28970-EN-150129
→
Selectthemenuitem"Device settings"with[->]andconrmwith
[OK].
Underthemenuitem"Device settings",youcanselecttherequested
application.Foralllevel,gaugeanddierentialmeasurements,the
application"Standard"iscorrect.
If an interface measurement should be carried out with a VEGAFLEX
67,youhavetochoosethemenuitem"Interface measurement"as
application.Afterthecongurationoftheinputs,theexactdielectric
constant for the upper medium must be entered. For further informa-
tionseechapter"Application examples".
→
Select the requested application with [->] and save your setting
with [OK].Finallychangetothemenuitem"Input"with[->].
Because VEGAMET 625 has two inputs, the measurement loops
must be assigned to the inputs. After the addresses of the HART sen-
sors are assigned, a list of the existing sensors can be prepared and
displayedvia"Sensor selection - Sensor search".Nowyoucanassign
the requested sensor to each measurement loop.
Fortransmission,VEGAMET625mustbeinformedwhich"Sensor
value
"shouldbeusedforfurtherprocessing.Dependingonthesen-
sor type this can be distance, pressure, interface or temperature. You
willndfurtherinformationunderthemenuitem"Meas. loop - Input".
→
Allocate the requested inputs to the appropriate measurement
loops, select the suitable sensor value and save your settings with
[OK].Aftertherstsetup,youcanmodifytheinputsalsounder
"Meas. loop - Input".
You can assign an unambiguous name to VEGAMET 625 via the
Device-TAG. This function is recommended when several instruments
are implemented and a good documentation of larger systems is
required.
→
Enter the requested values via the appropriate keys and save
your settings with [OK].
For instruments with integrated Ethernet interface, the automatic
addressing via DHCP is preset, i.e. the IP address must be assigned
by a DHCP server. Generally the instrument is contacted via the Host
Device settings - Applica-
tion
Device settings - Input
De
vice settings - Device-
TAG
Devicesettings-Host
Name/IP addr.