6 Setup with the integrated display and adjustment unit
VEGAMET 625 • Double channel HART
28970-EN-150129
Tosuppressuctuationsinthemeasuredvaluedisplay,e.g.caused
by an agitated product surface, an integration time can be set. This
time can be between 0 and 999 seconds. Remember that the reaction
time of the entire measurement will then be longer and the sensor will
react to measured value changes with a delay. In general, a period of
afewsecondsissucienttosmooththemeasuredvaluedisplay.
→
Enter the requested parameters via the appropriate keys and
save your settings with [OK].
Alinearizationisnecessaryforallvesselsinwhichthevesselvolume
does not increase linearly with the level, for example, with a cylindrical
orsphericaltank.Correspondinglinearizationcurvesareprepro-
grammed for these vessels. They represent the correlation between
the level percentage and vessel volume. By activating the appropriate
curve, the volume percentage of the vessel is displayed correctly. If
the volume should not be displayed in percent but e.g. in l or kg, a
scaling can be also set.
→
Enter the requested parameters via the appropriate keys and
save your settings with [OK].
Scaling means converting the measured value into a certain param-
eterandunit.Thelinearizedpercentagevalueisthesourcesignal
which is used as basis for the scaling. The indication can then show
the volume in litres e.g., instead of the percentage value. Indication
values from max. -99999 to +99999 are possible.
→
Enter the requested parameters via the appropriate keys and
save your settings with [OK].
In this menu item you can enter an unambiguous designation for each
measurement loop, e.g. the measurement loop name or the tank or
product designation. In digital systems and in the documentation
of larger plants, a singular designation should be entered for exact
identicationofindividualmeasuringpoints.
Meas. loop - Damping
Meas. loop - Linearization
curve
Meas. loop - Scaling
Meas. loop - Meas. loop
TAG