Operating instructions
24
6 Setup with the integrated display and adjustment unit
VEGAMET 625 • Double channel HART
28970-EN-150129
→
Enter the requested parameters via the appropriate keys and
save your settings with [OK].
Under"Outputs"youwillndtherelay/currentoutputs.Withrelay
output,rstofalltherequestedmode("Overll protection"or"Dry
running protection")mustbeselected.
•
Overllprotection:Relayisswitchedowhenthemax.levelis
exceeded (safe currentless state), relay is switched on again when
thelevelfallsbelowthemin.level(switch-onpoint<switch-o
point)
•
Dry run protection:Relayisswitchedowhenthelevelfalls
below the min. level (safe currentless state), relay is switched on
again when the max. level is exceeded (switch-on point > switch-
opoint)
Additionalmodessuchas"Switching window","Flow"and"Tenden-
cy
"canbeonlyadjustedviaPACTwareandDTM.
Select the requested mode and save with [OK]. By pushing [->], you
reach the next menu item.
1. Now enter the reference value to which the relay switching points
relate. By pushing [->], you reach the next menu item.
2. Enternowtheswitchingpointsforswitchingtherelayonando.
The parameter to which they refer can also be selected.
In the following window the reaction of the relay in case of failure can
bedetermined.Hereyoucandenewhether,incaseoffailure,the
switching condition of the relay remains unchanged or the relay is
switchedo.
The current output is used to transfer the measured value to a higher
ranking system, for example to a PLC, a control system or a meas-
ured value indication. This is an active output, i.e. a current is provided
actively. The processing unit must hence have a passive current input.
Meas. loop - Outputs -
Relaysoutputs
Meas. loop - Outputs -
Current outputs