Operating instructions

25
6 Setup with the integrated display and adjustment unit
VEGAMET 625 • Double channel HART
28970-EN-150129
The characteristics of the current outputs can be set to 0 … 20 mA,
4 … 20 mA or inverted. The reaction in case of failure can be also
adapted to the requirements. The parameter to which they refer can
also be selected.
→
Enter the requested parameters via the appropriate keys and
save your settings with [OK].
Inthemenuitem"Display - Indication value",youcansetthere-
quested indication value. The following options are available:
Percent: adjusted measured value without taking a probably
storedlinearizationintoaccount
Lin. percent: adjusted measured value by taking a probably
storedlinearizationintoaccount
Scaled: adjusted measured value by taking a probably stored
linarizationintoaccountaswellasthevaluesenteredunder"Scal-
ing"
Sensor value: input value delivered by the sensor. Presentation in
the selected adjustment unit
→
Enter the requested parameters via the appropriate keys and
save your settings with [OK].
When the instrument displays a failure message, further information is
availableunderthemenuitem"Diagnosis - Device status".
The simulation of a measured value is used to check the outputs and
connected components. The simulation can be applied to the percent-
age value, the lin. percentage value and the sensor value.
Note:
Please note that connected system parts (valves, pumps, motors,
controlsystems)areinuencedbythesimulation,thusunintentional
plant operating conditions can occur. The simulation is terminated
automatically after approxminately 10 minutes.
Display
Diagnostics
Service - Simulation