Operating instructions
43
8 Application examples
VEGAMET 625 • Double channel HART
28970-EN-150129
Further information on the dielectric constant are available in
the operating instructions manual of VEGAFLEX. For this appli-
cation, do not enter a dielectric constant directly on VEGAF-
LEX, because this value will be overwritten automatically by
VEGAMET 625
•
Adjustment
– Each VEGAFLEX is shipped with default settings. The values of
this adjustment are automatically tranferred to VEGAMET 625
during the setup of the interface measurement. Hence, manual
adjustment is usually not necessary. Should the instrument
require a special adjustment, this adjustment can be carried
outanytimeunder"Measurement loops - Adjustment".Keepin
mind that this adjustment must then be carried out separately
for all three measurement loops.
TS
d1
h1
h2
d2
1
L2
L1
Fig. 13: Interface measurement
1 Reference plane
d1 Distance to the interface, meas. loop 1
d2 Distance to the level, meas. loop 2
TS Thickness of the upper medium (d1-d2), meas. loop 3 (displayed value)
h1 Height - Interface (displayed value)
h2 Height - Level (displayed value)
L1 Lower medium
L2 Upper medium
Note:
WhenusingaVEGAFLEX8x,thissensormustrstbesetupfor
interface measurement. The VEGAFLEX must not be locked by the
PIN, because the VEGAMET requires write access.
8.4 Pumpcontrol1/2(runningtimecontrolled)
Pump control 1/2 is used to control several pumps with the same
function dependent on the previous running time. Always the pump
with the shortest running time is switched on and the pump with
thelongestrunningtimeswitchedo.Withincreasedrequirement,
all pumps can also run at the same time dependent on the entered
Functional principle