Operating instructions

46
8 Application examples
VEGAMET 625 • Double channel HART
28970-EN-150129
Measured value change higher: Measured value change per
time unit, at which the tendency recognition should respond
Max. reaction time: Time after which a new measured value
generation is carried out and the measured value change is
recalculated
Hysteresis:isautomaticallyalways10%ofthevalueof"Meas-
ured value change larger than"
Reactionincaseoffailure: In case of a failure, the relaygoes
intothedenedcondition
Note:
After switching on or a failure, always two complete cycles must be
executeduntilameasuredvaluedierencecanbecalculatedanda
tendency can be outputted.
The level in a basin should be monitored on rising tendency. If the rise
is higher than 25 % per minute, an additional emptying pumpt should
be switched on. The max. reaction time should be one minute. In case
ofaprobablefailure,thepumpshouldbeswitchedo.
SelectintheDTMnavigationsectionthemenuitems"Meas. loop -
Outputs - Relay".
E.g.setforrelay1themode"Rising tendency"
Selectunder"Reaction in case of failure"theoption"Switching
condition o"
Enterthefollowingvaluesintotheparameterelds:
Measured value more than 25 %/min.
Max. reaction time 1 min.
The function of the tendency recognition is shown in detail in the fol-
lowing diagram. The previously described example is used as a basis.
t
t
m
t
m
t
m
t
m
120 180 240
ON
OFF
60
[sec]
1 2 3 4
5
...
...
...
...
100
75
50
25
0
%
...
Fig. 15: Example for tendency recognition
1 Old average value = 25 %, new average value = 25 %
Dierence < 25 % -> Relay ON
2 Old average value = 25 %, new average value = 37.5 %
Dierence < 25 % -> Relay ON
3 Old average value = 37.5 %, new average value = 62.5 %
Dierence = 25 % -> Relay OFF
4 Old average value = 62.5 %, new average value = 75 %
Dierence < 25 % -> Relay ON
5 tm -> max. reaction time
Parameter
Example
Setup