28970-EN-150129
The signal conditioning instrument and the connected sensors are
permanently monitored during operation and the values entered dur-
ing parameter adjustment are checked for plausibility. If irregularities
occur or in case of incorrect parameter adjustment, a fault signal is
triggered. In case of an instrument defect or line break/shortcircuit, a
fault signal is also triggered.
The fail safe relay deenergises in case of failure, the failure indica-
tionlightsandthecurrentoutputsreactaccordingtotheircongured
control behaviour. In addition, one of the following fault messages is
outputted on the display.
Error code Cause Rectication
E003 CRC error (error with
self-check)
Carry out a reset
Send instrument for repair
E007 Sensor type not com-
patible
Search for sensor again and allocate
under"Meas. loop - Input"
E008 Sensor not found
Check connection of the sensor
Check HART address of the sensor
E011 No HART sensor as-
signed
Assignasensorinthemenu"Input"
E013 Sensor signals error,
no valid measured
value
Check sensor parameter adjustment
Send sensor for repair
E016 Empty/full adjustment
reversed
Carry out a fresh adjustment
E017 Adjustment span too
small
Carry out a fresh adjustment and
increase the distance between min.
and max. adjustment
E021 Scaling span too
small
Carry out a fresh scaling, increase
the distance between min. and max.
scaling.
E026 Units of the input
variablearedier-
ent(onlydierential
measurement loop)
Adapt the units of both
Use sensors with the same input
variable
E030 Sensor in boot phase
Measured value not
valid
Check sensor parameter adjustment
E034 EEPROM CRC error
Switchtheinstrumentoandon
Carry out a reset
Send instrument for repair
E035 ROM CRC error
Switchtheinstrumentoandon
Carry out a reset
Send instrument for repair
E036 Instrument software
not executable (dur-
ing software update
and after failed up-
date)
Waiting until software update is
nished
Carry out another software update
Fault message