Operating instructions
51
9Maintenanceandfaultrectication
VEGAMET 625 • Double channel HART
28970-EN-150129
Error code Cause Rectication
E053 Sensor measuring
range is not read cor-
rectly
– Communication error: Check sensor
cable and screening
E062 Pulse priority too
small
– Increaseunder"Output"theentry
"Pulse output all"sothatmax.one
pulse per second is outputted.
E110 Relay switching
points too close to-
gether
– Increasethedierencebetweenthe
two relay switching points
E111 Relay switching
points interchanged
– Change relay switching points for
"On/O"
E115 Several relays are as-
signef to the pump
control which are not
set to the same fail-
ure mode
– All relays which are assigned to the
pump control must be set to the
same failure mode
E116 Several relays that
arenotcongured
with the same mode
are assigned to the
pump control
– All relays which are assigned to the
pump control must be set to the
same mode
Depending on the reason for the fault and the measures taken, the
stepsdescribedinchapter"Set up"mayhavetobecarriedoutagain.
9.3 Howtoproceedifarepairisneeded
Youcanndarepairformaswellasdetailedinformationonhowto
proceed at www.vega.com/downloadsand"Forms and certicates".
By doing this you help us carry out the repair quickly and without hav-
ing to call back for needed information.
If a repair is necessary, please proceed as follows:
•
Printandlloutoneformperinstrument
•
Clean the instrument and pack it damage-proof
•
Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
•
Please contact the agency serving you to get the address for
thereturnshipment.Youcanndtheagencyonourhomepage
www.vega.com.
Reactionafterfaultrecti-
cation