Operating instructions
55
11 Supplement
VEGAMET 625 • Double channel HART
28970-EN-150129
Operation
Adjustment elements
4 x keys for menu adjustment
PC adjustment PACTware with respective DTM
Ambient conditions
Ambient temperature
-20 … +60 °C (-4 … +140 °F)
Storage and transport temperature -40 … +80 °C (-40 … +176 °F)
Electrical protective measures
Protection rating
Ʋ Instrument IP 30
Ʋ Terminal socket IP 20
Overvoltage category II
Protection class II
Electrical separating measures
Reliable separation according to VDE 0106 part 1 between power supply, input and digital compo-
nent
Ʋ Reference voltage 250 V
Ʋ Voltage resistance of the isolation 3.75 kV
Galvanic separation between relay output and digital part
Ʋ Reference voltage 250 V
Ʋ Voltage resistance of the isolation 4 kV
Potential separation between Ethernet interface and digital part
Ʋ Reference voltage 50 V
Ʋ Voltage resistance of the isolation 1 kV
Potential separation between RS232 interface and digital part
Ʋ Reference voltage 50 V
Ʋ Voltage resistance of the isolation 50 V
Approvals
Instrumentswithapprovalscanhavedierenttechnicalspecicationsdependingontheversion.
For that reason the associated approval documents of these instruments have to be carefully
noted. They are part of the delivery or can be downloaded under www.vega.comvia"VEGA Tools"
and"Instrument search"aswellasvia"Downloads"and"Approvals".
11.2 Overview applications/functionality
The following charts provide an overview of the standard applications and functions of signal condi-
tioning instruments VEGAMET 391/624/625 and VEGASCAN 693. They also give information about
whether the respective function can be activated and adjusted via the integrated indicating and
adjustment unit (OP) or via PACTware/DTM.