User manual

94 vacon parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
8.17 Motor Pre-heat (Control panel: Menu PAR -> P16)
8.18 Easy usage menu (Control panel: Menu PAR -> P17)
Code Parameter Min Max Unit Default ID Note
P16.1
Motor Pre-heat
Function
02 01225
0 = Not used
1 = Always in stop state
2 = Controlled by digital
input
P16.2
Motor Pre-heat
Current
0
0,5 x
I
Nunit
A 0 1227
DC current for Pre-heat-
ing of motor and drive in
stop state. Active in stop
state or by digital input
while in stop state.
Table 8.17: Motor Pre-heat
Code Parameter Min Max Unit Default ID Note
Application Type 0 3 0 540
0 = Basic
1 = Pump
2 = Fan drive
3 = High Torque
NOTE! Visible only when
Startup wizard is active.
P17.2
Parameter
conceal
0 1 1 115
0 = All parameters visible
1 = Only quick setup
parameter group visible
P17.3
Temperature
unit
0 1 0 1197
0 = Celsius
1 = Kelvins
NOTE! Hidden until an
OPTBH board is con-
nected.
P17.4
Application
access pass-
word*
0 30000 0 2362
Input the right password
could review parameter
group 18.
Table 8.18: Easy usage menu parameters
NOTE!
* These parameters are only available in power SW FWP00001V026 included in
FW01070V010 or later version.
P17.1
i