parameters vacon • 95
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
8.19 System parameters
Code Parameter Min Max Default ID Note
Software information (MENU SYS->V1)
V1.1 API SW ID 2314
V1.2 API SW version 835
V1.3 Power SW ID 2315
V1.4 Power SW version 834
V1.5 Application ID 837
V1.6 Application revision 838
V1.7 System load 839
When no field bus Option Board or no OPT-BH Board has been installed, the Modbus comm.
Parameters are as follows
V2.1 Communication status 808
Status of Modbus
communication.
Format: xx.yyy
where xx = 0 - 64 (Num-
ber of error messages)
yyy = 0 - 999 (Number of
good messages)
P2.2 Fieldbus protocol 0 1 0 809
0 = Not used
1 = Modbus used
P2.3 Slave address 1 255 1 810
P2.4 Baud rate 0 8 5 811
0 = 300
1 = 600
2 = 1200
3 = 2400
4 = 4800
5 = 9600
6 = 19200
7 = 38400
8 = 57600
P2.6 Parity type 0 2 0 813
0 = None
1 = Even
2 = Odd
The Stop Bit is 2-bit
When Parity type is
0 = None;
The Stop Bit is 1-bit
When Parity type is
1 = Even or 2 = Odd
Table 8.19: System parameters