User manual

96 vacon parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
P2.7 Communication time out 0 255 10 814
0 = Not used
1 = 1 sec
2 = 2 secs, etc
P2.8
Reset communication
status
0 1 0 815
When Canopen E6 board has been installed, the comm. Parameters are as follows
V2.1
Canopen communication
status
14004
0 = Initialising
4 = Stopped
5 = Operational
6 = Pre_Operational
7 = Reset_Application
8 = Reset_Comm
9 = Unknow
P2.2 Canopen operation mode 1 2 1 14003
1 = Driver Profile
2 = Bypass
P2.3 Canopen Node ID 1 127 1 14001
P2.4 Canopen baud rate 3 8 6 14002
3 = 50 kBaud
4 = 100 kBaud
5 = 125 kBaud
6 = 250 kBaud
7 = 500 kBaud
8 = 1000 kBaud
When DeviceNet E7 board has been installed, the comm. Parameters are as follows
V2.1 Communication status 14014
Status of Modbus com-
munication. Format:
XXXX.Y, X = Device-
Net msg counter,
Y = DeviceNet status.
0 = Non-existent or no
bus power.
1 = Configuring state
2 = Established
3 = Timeout
P2.2 Output assembly type 20 111 21 14012 20, 21, 23, 25, 101, 111
P2.3 MAC ID 0 63 63 14010
P2.4 Baud rate 1 3 1 14011
1 = 125 kbit/s
2 = 250 kbit/s
3 = 500 kbit/s
P2.5 Input assembly type 70 117 71 14013 70, 71, 73, 75, 107, 117
Code Parameter Min Max Default ID Note
Table 8.19: System parameters