124 • vacon parameter descriptions
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
9
9.8 Digital outputs (Control panel: Menu PAR -> P8)
8.1 RO1 SIGNAL SELECTION
8.2 RO2 SIGNAL SELCETION
8.3 DO1 SIGNAL SELCETION
Table 9.2: Output signals via RO1, RO2 and DO1
Setting Signal content
0 = No
t used Output is not in operation.
1 = Ready The frequency converter is ready to operate.
2 = Ru
n The frequency converter operates (motor is running).
3 = Fault A fault trip has occurred.
4 = Fa
ult inverted A fault trip has not occurred.
5 = Warning A warning is active.
6 = Re
versed
The reverse command has been selected, output fre-
quency to the motor is negative.
7 = At speed The output frequency has reached the set reference.
8 = M
otor regulator active
Each of Motor regulator is active (e.g., over current
regulator, over voltage regulator, under voltage reg-
ulator, etc.)
9 = FB Control Word.B13
Output can be controlled with B13 in the fieldbus control
word.
10 = F
B Control Word.B14
Output can be controlled with B14 in the fieldbus control
word.
11 = FB Control Word.B15
Output can be controlled with B15 in the fieldbus control
word.
12 = Ou
tput frequency superv.
Output frequency is over / under the limits, set with
parameters P12.1 and P12.2.
13 = Output torque superv.
Motor torque is over/under the limit, se t with parameter
P12.3 and P12.4
14 = Un
it temperature superv.
Unit temperature is over / under the limits, set with
parameters P12.5 and P12.6.
15 = Analogue input superv.
Analogue inputs set with parameter P12.7 is over / under
the limits, set in P12.8 and P12.9.
16 = Pr
eset Speed Active Each of preset speeds are activated.
17 = External Brake control
External Brake control. Closed = Brake open,
Open = Brake closed.
18 = K
eypad control active Keypad is set as the current control place.
19 = I / O control active I / O is set as the current control place.