126 • vacon parameter descriptions
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
9
9.10 Fieldbus Data-Mapping (Control panel: Menu PAR -> P10)
10.1 FB DATA OUT 1 SELECTION
Parameter couples read only variables to output process data 1.
0 = Frequency reference
1 = Output reference
2 = Motor speed
3 = Motor current
4 = Motor voltage
5 = Motor torque
6 = Motor power
7 = DC link voltage
8 = Active fault code
9 = Analogue AI1
10 = Analogue AI2
11 = Digital input state
12 = PID feedback value
13 = PID setpoint
14 = Pulse train / encoder input(%)
15 = Pulse train / encoder pulse()
10.9 AUX CW DATA IN SELECTION
Parameter defines the input process data coupled to Aux Control Word.
0 = Not used
1 = PDI1
2 = PDI2
3 = PDI3
4 = PDI4
5 = PDI5