Underload curve at
zero freq.
P13.15= 10%
f
5Hz
Underload cu rve at
Field weakening
point, P1.11
Underload area
To rq ue
Feild weakening point,
P13.14(default)=50%
parameter descriptions vacon • 129
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
Figure 9.17: Underload protection
13.7 MOTOR THERMAL PROTECTION
0 = No action
1 = Alarm
2 = Fault, stop function
3 = Fault, coast
If tripping is selected the drive will stop and activate the fault stage, if the tem-
perature of the motor becomes too high. Deactivating the protection, i.e. set-
ting parameter to 0, will reset the thermal model of the motor to 0%.
The motor thermal protection is to protect the motor from overheating. The drive is
capable of supplying higher than nominal current to the motor. If the load requires
this high current there is a risk that the motor will be thermally overloaded. This is
the case especially at low frequencies. At low frequencies the cooling effect of the
motor is reduced as well as its capacity. If the motor is equipped with an external fan
the load reduction at low speeds is small.
The motor thermal protection is based on a calculated model and it uses the output
current of the drive to determine the load on the motor.
The motor thermal protection can be adjusted with parameters. The thermal current
I
T
specifies the load current above which the motor is overloaded. This current limit
is a function of the output frequency.
The thermal stage of the motor can be monitored on the control keypad display.
CAUTION! The calculated model does not protect the motor if
the airflow to the motor is reduced by blocked air intake grill.