parameter descriptions vacon • 135
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
9.13 Automatic reset (Control panel: Menu PAR -> P14)
14.1 AUTOMATIC RESET
Activate the Automatic reset after fault with this parameter.
NOTE: Automatic reset is allowed for certain faults only.
Fault: 1. Under voltage
2. Over voltage
3. Over current
4. Motor over temperature
5. Under load
14.3 TRIAL TIME
The Automatic restart function restarts the frequency converter when the
faults have disappeared and the waiting time has elapsed.
The time count starts from the first auto reset. If the number of faults occur-
ring during the trial time exceeds trail number (the value of P14.4), the fault
state becomes active. Otherwise the fault is cleared after the trial time has
elapsed and the next fault starts the trial time count again. See Figure 9.23.
If a single fault remains during the trial time, a fault state is true.
Fault trigger
Motor stop signal
Mot or
start signal
Supervision
Restart 1 Restart 2
Trial ti me
par.14.3
Fault active
RESET/
Fault reset
Autor
e
set function: (Trials = 2)
Wait time
pa r.14.2
Wait t ime
pa r.14.2
Wait t ime
pa r.1 4. 2
Figure 9.23: Example of Automatic restarts with two restarts