9.17.3 Modbus process data
Process data is an address area for fieldbus control. Fieldbus control is active when
the value of parameter 2.1 (Control place) is 1 (= fieldbus). The content of the process
data can be programmed in the application.The following tables present the process
data contents in Vacon20 Application.
ID Modbus register Name Scale Type
2101 32101, 42101 FB Status Word - Binary coded
2102 32102, 42102 FB General Status Word - Binary coded
2103 32103, 42103 Reserved 0,01 %
2104 32104, 42104
Programmable by P10.1
(Default: Frequency reference)
--
2105 32105, 42105
Programmable by P10.2
(Default: Output frequency)
0,01 +/- Hz
2106 32106, 42106
Programmable by P10.3
(Default: Motor speed)
1+/- Rpm
2107 32107, 42107
Programmable by P10.4
(Default: Motor voltage)
0,1 V
2108 32108, 42108
Programmable by P10.5
(Default: Motor torque)
0,1
+/- % (of nomi-
nal)
2109 32109, 42109
Programmable by P10.6
(Default: Motor current)
0,01 A
2110 32110, 42110
Programmable by P10.7
(Default: Motor power)
0,1
+/- % (of nomi-
nal)
2111 32111, 42111
Programmable by P10.8
(Default: DC link voltage)
1V
Table 9.4: Output process data
ID Modbus register Name Scale Type
2001 32001, 42001 FB Control Word - Binary coded
2002 32002, 42002 FB General Control Word - Binary coded
2003 32003, 42003 Reserved 0,01 %
2004 32004, 42004 Programmable by P10.9
2005 32005, 42005 Programmable by P10.9
2006 32006, 42006 Programmable by P10.9
2007 32007, 42007 Programmable by P10.9
2008 32008, 42008 Programmable by P10.9
Table 9.5: Input process data